215
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
,
b
failure of fan motor
• This alarm is indicated when the revolution pulse output from the fan motor is the reverse revolution signal is detected.
The fan motor is stopped once, and restarted after 10 seconds. If it occurs more than 10 times in 30 minutes, this
alarm is indicated.
Alarm code fan Motor
MF1
b
MF2
note
Check to ensure that DC Fan Motor is checked according to the
-
section "Fault diagnosis of DC fan motor".
In the case that the fan motor does not run
even the PCB1 is replaced, replace fan inverter
PCB (PCB4,5).
Yes
This alarm is indicated due
to detected overcurrent by
the contrary wind. This is
normal.
Does the motor run?
Check the connector connection
of CN14 and CN15 (on PCB1) and
CN201, CN202, PCN201, PCN203 (on
PCB3,4).
Faulty
Restart operation
No
Alarm code is not indicated
Are the connectors abnormal?
Connect it correctly.
Restart operation
Does the motor run?
This is normal
Replace the fan motor
Restart operation
Does the motor run?
Yes
Good
This is normal
Yes
No
Alarm code is not indicated
Replace the PCB1
No