Troubleshooting
Service Manual
220
Checking procedure for main parts
SMGB0066 rev.0 - 12/2009
7.4.2. rHUE-(5/6)AHn. Procedure for checking the ISPM.
● Procedure using an analog tester:
Checking the diode module:
By touching the + side of the tester to the P1
1.
terminal of ISPM and the - side of the tester to R
and S of ISPM, measure the resistance. If all the
resistances are more than 1 kΩ, it is normal.
By touching the - side of the tester to the P1
2.
terminal of ISPM and the + side of the tester to R
and S of ISPM, measure the resistance. If all the
resistances are more than 100 kΩ, it is normal.
By touching the - side of the tester to the N
3.
terminal of ISPM and the + side of the tester to R
and S of ISPM, measure the resistance. If all the
resistances are more than 1 kΩ, it is normal.
By touching the + side of the tester to the N
4.
terminal of ISPM and the - side of the tester to R
and S of ISPM, measure the resistance. If all the
resistances are more than 100 kΩ, it is normal.
Remove all the terminals of the ISPM before check.
If items (a) to (h) are performed and the results are satisfactory, ISPM is
normal. Measure it under 1 kΩ range of a tester.
warning
Electrical hazard. Risk of electrical shock. Perform the high voltage discharge procedure as described.
-
Capacitors
LED 201
Noise filter PCB
Fuses
Reactor
Magnetic contactor
Magnetic contactor
Inverter module ISPM
Rectification parts of internal circuit of ISPM (common)