Troubleshooting
Service Manual
224
Checking procedure for main parts
SMGB0066 rev.0 - 12/2009
Measurement procedure
1.
Remove the fan motor connector from the control PCB, ISPM or
DIP-IPM.
2.
Connect the black test lead of the tester to the black wire pin of
the fan motor connector
3.
Connect the red test lead to the wire connector pin to be checked
Results
Normal:
Observed values will be close to the normal values in the table
below
Faulty:
Observed values will be deviated from the normal values in the
table below.
Generaly an open-circuit fault shows ∞, and a short-circuit fault
shows several Ω-kΩ.)
Internal electronic circuit fault of the fan motor including short-circuit and breakage can be checked.
Model
Motor model
Wire color for checking (normal value) Ω
red-black
White-black
yellow-black
Blue-black
RHUE-(3~6)A(V)HN
SIC-68FV-D851-7.8
1 MΩ or greater
42-78 KΩ
168-312 KΩ
1 MΩ or greater
(*) Values are shown for referenctial purpose. While actual values may vary depending on the type of the tester; any tester can be
used to determine any short-circuit or breakage based on ∞ or several Ω/several kΩ or 0Ω.
• other parts
Part name
Unit models
Model code
resistance (
W
)
Solenoid valve for gas bypass
105-52-52 (50Hz)
1540.00
at 20 ºC
Solenoid valve for liquid injection
105-52-52 (50Hz)
1540.00
at 20ºC
Reversing valve
STF-01AJ502D1 (50Hz)
1435.00
at 20ºC
Compressor motor
RHUE-(3/4)AVHN
EK306AHD-27A2
0.24
at 20ºC
EK406AHD-36A2
0.20
at 20ºC
RHUE-(5/6)AVHN
RHUE-(5/6)AHN
EK405AHD-36D2
0.239
at 20ºC