243
RHUE-(3~6)A(V)HN
SMGB0066 rev.0 - 12/2009
Servicing
Service Manual
9
Thermistor
holder
Holder
Td
Thermistor
Thermistor
fixing plate
Indication of
terminal number
Terminal box cover
Rubber cap Th
Thermistor
Compressor
Compressor
wires
Details for compressor terminals
Fix it with screw
Compressor
wires (3 wires)
note
Do not expose the refrigerant cycle to the atmosphere
-
for a long period in order to avoid water and foreign
particles entering into the refrigerant cycle. After removing
the compressor, replace it quickly. If it is exposed to
the ambiance for a long period, seal both suction and
discharge pipes.
Remove the cap for the compressor just before replacing
-
the compressor. Before assembling the compressor, seal
the suction pipe and discharge pipe with tape to protect
the compressor interior from foreign particles. Remove the
tape when connecting the pipes.
warning
Flamable objects. Fire risk. All compressor pipes must be
-
brazed to be connected to the refrigerant circuit. Ensure
that all the sourrounding is free of flammable objects and
liquids when performing piping brazing work.