Servicing
Service Manual
246
RHUE-(3~6)A(V)HN
SMGB0066 rev.0 - 12/2009
9.1.9. opening electrical box
(P-mounting plate)
Remove the service cover according to the section
1.
“Removing the service cover” in this chapter.
Remove the five (5) screws fixing the electrical
-
box. Open the P-mounting plate by rotating it 90
degrees to the left.
danger
Electrical hazard. Risk of death.
-
Check that the LED201 (red) located on the inverter
-
module is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201
-
(Red) located on the inverter module is ON in order to
avoid an electrical shock.
2 screws
1 screw
2 screws
P-Mounting plate