9
9.1.19. removing the dIP-IPM
The DIP-IPM is equiped in the RHUE-(3~6)AVHN units.
danger
Electrical hazard. Risk of death.
-
Check that the LED201 (red) located on the inverter
-
module is OFF when opening the P-mounting plate.
Do not touch the electrical components when LED201
-
(Red) located on the inverter module is ON in order to
avoid an electrical shock.
Disconnect all the wirings connected to the module.
1.
Disconnect the wirings of the ter,- , U, V, W
-
Disconnect all the wirings connected to the module.
2.
Remove the four (4) fixing screws on the DIP-IPM
-
module to remove it.
note
Several hazards. Risk of malfunction.
-
Identify the terminal numbers with mark band. When
-
reassembling, the terminals have to be connected to the
correct numbers . If incorrectly connected, malfunctions
or damages will occur.
Check to ensure that the electrical wires will not be
-
caught between the mounting electrical components and
the mounting plates when the PCB is remounted.
Apply silicon grease evenly on the whole rear side of the
-
diode module and the transistor module when mounting.
Silicon grease is available as a field-supplied accessory.
DIP-IPM module
4 fixing screws
LED201