Water pipe
installation
Service Manual
36
Piping work connection considerations
SMGB0066 rev.0 - 12/2009
note
(1)
-
The shaded part of the pipe system below. (Excluding the expansion tank (cistern))
Calculate and ensure that the water volume in the system is equal or greater than the larger value obtained from:
Protective water volume for product
1.
Minimum water volume for temperature drop during defrost operation
2.
When the minimum water volume can not be ensured, use a Buffer tank to compensate the shortage (<0) of water (2). See
figure below.
Expansion tank
Pump
Yutaki unit
Load
system
Expansion tank
Pump
Yutaki unit
Buffer tank
Load
system
note
(2)
-
Shortage = Minimum water volume – Water volume in circulation system
The following part shows the minimum water volume in the system for product protection and temperature drop during
defrost operation.
Protective water volume for product
1.
Ensure that the water volume is equal or greater than those shown below, in order to reduce ON/OFF frequency of the unit
at no load or extreme light load. When water volume is less than the volume indicated (minimum water volume), compressor
operation frequently stops at light load, which may result in shorter life or failure.
Model
ON/OFF
Temp. differential
rHUE-3AVHn
rHUE-4AVHn
rHUE-5A(V)Hn
rHUE-6A(V)Hn
4ºC
28
38
46
56
3ºC
36
48
58
70
2ºC
50
65
80
96
1ºC
80
107
130
156
(Units are in ltrs.)