53
LED indication
SMGB0066 rev.0 - 12/2009
Electrical wiring
Service Manual
3
● Jumper lead setting (JP2): Automatic restart after power failure
Keep the same status as before. Setting before shipment:
JP2
1
0 = open; 1 = Short circuit
The function selection using the jumper lead setting is shown in the table below.
Setting
function
details
0
Enable
If this function is 'Enable', in case of power failure the unit will restart
automatically once the power is recovered
1
Disable
3.4. lEd IndICATIon
• lEd1, lEd2 and lEd3: Power supply indication
Status
lEd1
lEd2
lEd3
Power supply ON
ON
OFF
OFF
Power supply OFF
OFF
OFF
OFF
Not available for Yutaki
• lEd4: operation status indication
Status
lEd4
Unit stopped
OFF
Unit running
ON
Alarm
OFF
• lEd5: Alarm indication
Status
lEd5
Normal
OFF
Alarm
ON
• lEd6: Setting mode indication
Status
lEd6
Setting mode disable
OFF
Setting mode enable
(DSW1#3: ON)
ON