Controller pack
Service Manual
94
Heatpump control functions
SMGB0066 rev.0 - 12/2009
Parameter Settings
•
P14 / EP14 Heat Pump minimum outdoor temperature (default -20°C)
EP28
Heat Pump minimum supply temperature below outdoor temperature of EP32 (default 35°C)
EP29
Heat Pump maximum supply temperature above outdoor temperature of EP34 (default 55°C)
EP32
Heat Pump minimum supply inflexion point (default 0°C)
EP33
Heat Pump maximum supply temperature below outdoor temperature of EP34 (default 50°C)
EP34
Heat Pump maximum supply changing point (default -10°C)
note
Engineering Parameters (EP) are only available for service engineers.
-
4.5.6. Tariff Switch (Heat Pump blocking) Input
Configuration Specific
•
The tariff switch input (heat pump blocking) is only allowed for Bi-Valent systems. For mono-valent or mono-energetic
systems the heat pump can never be blocked by this input.
function
•
This function allows an external tariff-switch device to switch off the heat pump during times of peak electricity demand.
When the controller is working in bi-valent mode, the boiler will be switched on to provide the necessary heating.
Parameter Setting
•
P24 Configuration of Tariff/Timer Input (default 4)
P24
open Circuit on terminals 10/11
Closed Circuit on terminals 10/11
0
Tariff/Timer input is ignored
1
Heat Pump is enabled
Heat Pump is blocked
2
Heat Pump is blocked
Heat Pump is enabled
3
Tariff/Timer input is used for DHW time clock
4
Tariff/Timer input is used for DWH time clock
note
The tariff/timer input can be used for DHW time switching OR Heat Pump blocking, not both.
-