4 HANDLING
4-15
(c) Control
code
When implementing a preset start and a comparator value set, write the preset or
comparator value to the write data area before setting a control code in it.
EW
0+10
Control code
2
0
2
15
2
4
2
3
No effect
Q
Operation mode 1
Control code
Explanation
Action when set
8
Count stop
Stops pulse measurement.
4 Preset
start
Sets a preset value in the counter and starts
measurement.
2
Compare value set
Sets a compare value in the comparator
register and starts measurement.
1 Latch
reset
Resets the match output signal latched and
starts measurement.
None of above
No effect
−
Q
Operation mode 2
Control code
Explanation
Action when set
8
Count stop
Stops pulse measurement.
4 Preset
start
Sets a preset value in the counter and starts
measurement.
2
Compare value set
Sets a compare value in the comparator
register.
1 Latch
reset
Resets the match output signal latched.
None of above
No effect
−
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...