6 HANDLING I/O DATA ON D.Station
6-2
6.1 Digital Input/Digital Output/Digital I/O Modules
The data formats that work in normal transfer mode and in analog 4-bit shift mode are the same
as those for transferring I/O data on remote I/O.
6.2 Pulse Counter Modules
Table 6-1 Pulse Counter Module Data Format
Data transfer mode
Data format
Normal transfer mode
MSB
2
15
2
2
2
1
2
0
Read/write count data
Control code
Status code when read
Control code
Mode 1
Mode 2
0 0
Counter stop
Counter stop
0 1
Preset start
Preset start
1 0
Compare value set
Compare value set
1 1
Latch reset
Latch reset
Status code
Mode 1
Mode 2
0 0
Counter stop
Counter stop
0 1
R>C
Preset start
1 0
R=C
Compare value set
1 1
R<C
Latch reset
Analog 4-bit shift mode
Not usable
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...