1 BEFORE USE
1-3
(3) Use the PCs within the limits of environmental specifications defined below. Its operation
under room temperature, room humidity conditions of usage (15 to 35ºC, 45 to 85% RH) is
recommended to keep it running successfully for extended periods of time. Using the product in
a hot and humid environment or in a place where there are sharp temperature changes within a
day will degrade its service life.
Supply voltage
LQV000: 100 to 120 VAC
Single phase 50/60 Hz ± 5 Hz
LQV100: 100 to 120 VAC
Single phase 50/60 Hz ± 5 Hz
100 to 110 VDC
LQV020: 24 VDC
LQV200: 200 to 240 VDC
Single phase 50/60 Hz ± 5 Hz
Supply voltage
fluctuations
LQV000: 85 to 132 VAC
LQV100: 85 to 132 VAC
85 to 132 VDC
LQV020: 20.4 to 28.8 VDC
LQV200: 170 to 264 VAC
Temperature
Operating: 0 to 55ºC, Storage: -20 to 75ºC
(Temperature change rate: 10ºC /h or lower)
Relative humidity
Operating: 30 to 90% RH, Storage: 10 to 90% RH
(non-condensing)
Vibration resistance
Compliant with JIS C0040
Frequency: 10 to 150 Hz, Acceleration: 10 m/s
2
8-minute sweep in each of the X-/Y-/Z-axis directions, 20 sweep cycles
Shock resistance
Compliant with JIS C0041i
Peak acceleration: 147 m/s
2
Sinusoidal half-wave pulses, three cycles in each of the X-/Y-/Z-axis directions
Ambient air
Dust class: One million, no corrosive gases
CAUTION
If the input voltage of the power supply module is within its specified range but it
is closer to the upper or lower limit of the range, assume an input power supply
error and request inspection from the power supply facility administrator.
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...