1 BEFORE USE
1-6
(11) Grounding
Inspection of the ground wiring:
y
Check if a ground wire is shared with another ground wire.
y
Check if the grounding point is at least 15 m away from the grounding point of the AC panel.
y
Check if any power cables or lead cables (e.g., a motor lead cable) are located adjacent to the
signal cables, such as the remote I/O cable.
S10mini
S10mini Other
devices
Isolation of grounding wires
Other devices
Share of grounding wires
WARNING
z
Build an emergency stop circuit, interlock circuits and so forth outside this
product. If these circuits were built inside the product, its failures could result
in damage to hardware or in accidents.
z
Limit the I/O current through an I/O module to the maximum allowable current
rating or below. Overcurrent flow through an I/O module could cause
damage to its internal components, resulting in accidents, fires and failures.
z
Use an external power supply equipped with overvoltage and overcurrent
protection features.
z
If the product smokes, smells offensively or otherwise appears to be
misbehaving, switch it off immediately and start problem determination.
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...