2 KINDS AND SPECIFICATIONS OF I/O MODULES
2-6
Type LQY170
Output format
Contact output
Number of outputs 6
outputs (a-contacts × 2, c-contacts × 4)
Number of commons
None (All points: Independent)
Insulation method
Relay
Rated output voltage
100 to 240 VAC,
12 to 24 VDC
Rated output current
2.0 A/output
Response
time
OFF
→
ON
15 ms or less
ON
→
OFF
15 ms or less
Internal current dissipation
320 mA or less
External wiring connection method
18-point terminal block
Operation indication
LED indication (lit when ON)
Mass 250
g
Combining
mount
base
CPU unit mount base
Mountable
I/O unit mount base
Mountable
Scan-type analog input
module mount base
Mountable
Type LQY200
Output format
Transistor output (sink)
Number of outputs 16
outputs
Number of commons
16 common
Insulation method
Photocoupler
Rated output voltage
12 to 24 VDC
Maximum output current
0.3 A/output
Response
time
OFF
→
ON
0.2 ms or less
ON
→
OFF
0.3 ms or less (resistive load)
Internal current dissipation
120 mA or less
External
power
supplies
Voltage
10.2 to 26.4 VDC
Current (n: Number of
ON points)
3.5 mA × n (12 VDC)
7.0 mA × n (24 VDC)
External wiring connection method
18-point terminal block
Operation indication
LED indication (lit when ON)
Mass 210
g
Combining
mount
base
CPU unit mount base
Mountable
I/O unit mount base
Mountable
Scan-type analog input
module mount base
Mountable
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...