2 KINDS AND SPECIFICATIONS OF I/O MODULES
2-13
2.2 Mounting
Design
Before installing I/O modules in the CPU or I/O mounting base, make sure that the sum total of
their current dissipations does not exceed the rating for the power supply module. Table 2-1
gives the current dissipation of each type of module, and Figure 2-1 shows the maximum output
current rating of the power supply module. Table 2-2 indicates the maximum number of
modules that can be mounted for operation at room temperature. Depending on the
combination of modules that are mounted, free slots may have to be made available. For more
information, see Section 4.1, “Mounting I/O Modules.”
Table 2-1 Module Current Dissipation Values
(1/2)
Description Type
Current
dissipation
CPU module
LQP***
1,500 mA or less
Station module
LQS000
150 mA or less
LQS020
700 mA or less
Digital input module
LQX110
110 mA or less
LQX130
70 mA or less
LQX150
110 mA or less
LQX151
110 mA or less
LQX200
80 mA or less
LQX201
80 mA or less
LQX210
110 mA or less
LQX211
170 mA or less
LQX220
110 mA or less
LQX240
110 mA or less
LQX250
110 mA or less
LQX300
150 mA or less
LQX310
150 mA or less
LQX350
170 mA or less
LQX360
170 mA or less
Digital output module
LQY100
780 mA or less
LQY140
400 mA or less
LQY150
800 mA or less
LQY160
320 mA or less
LQY170
320 mA or less
LQY200
120 mA or less
LQY300
260 mA or less
LQY310
260 mA or less
LQY350
400 mA or less
LQY360
400 mA or less
Digital I/O module
LQZ300
300 mA or less
Pulse counter module
LQC000
150 mA or less
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...