3 INDIVIDUAL SPECIFICATIONS
3-20
3.15 LQY140 (Contact outputs, a-contacts × 8)
Table 3-19 LQY140 Specifications
Item Specification
Number of outputs
8 outputs (a-contacts × 8)
Insulation method
Relay insulation
Rated output
100 to 250 VAC: 2.0 A/output
12 to 24 VDC: 2.0 A/output
48 VDC:
0.5 A/output
100 to 110 VDC: 0.1 A/output
Maximum output voltage
250 VAC, 125 VDC
Minimum output current
100 to 220 VAC:
10 mA
48 VDC, 100 to 110 VDC: 10 mA
12 to 24 VDC:
20 mA
Maximum rush current
5 A, 100 ms or less
Response time
OFF
→
ON
15 ms or less
ON
→
OFF
15 ms or less
Maximum switching frequency 1,800
cycles/hour
Service life (electrical) of relay
Approx. 70,000 cycles of make-and-break operation (2 A
at 220 VAC [COS
φ
= 0.4], 2 A at 24 VDC [L/R = 7 ms],
make-and-break operation frequency of 1,800 cycles per
hour, normal temperature and normal humidity)
Internal current dissipation
400 mA or less
Number of commons
One input/common (independent common)
Dielectric voltage
1,500 VAC, 1 minute (between external terminals in a
batch and ground)
External
wiring
Connection method
18-point terminal block connector (screw: M3)
Compatible wire
0.3 to 1.25 mm
2
Tightening torque
Approx. 6 to 8 N
・
m
Allowable wiring length
200 m
Operation indication
LED indication (lit when ON); color: green
Mass 220
g
Fuse (*)
B2
A1
0
C0
7
B9
A8 C7
Output indication LED
RY
L
L
Load
RY
Control circuit
(*) Install a fuse to meet the following requirements:
y
Rated breaking current of 5 A
y
Install a fuse on the positive side of a DC load, or on both sides of an AC load.
Figure 3-32 LQY140 Circuit
A1
A2
A3
A4
A5
A6
A7
A8
A9
B1
B2
B3
B4
B5
B6
B7
B8
B9
100-120 VAC, 12-24 VDC
LQY140
D.OUTPUT
3
2
1
0
7
6
5
4
0
C0
NOT
USED
NOT
USED
C1
C2
C3
C4
C5
C6
C7
1
2
3
4
5
6
7
Figure 3-31 LQY140
Appearance
Summary of Contents for S10mini LQS070
Page 1: ......
Page 2: ......
Page 19: ...This Page Intentionally Left Blank ...
Page 30: ...1 BEFORE USE ...
Page 37: ...This Page Intentionally Left Blank ...
Page 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Page 57: ...This Page Intentionally Left Blank ...
Page 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Page 143: ...This Page Intentionally Left Blank ...
Page 144: ...4 HANDLING ...
Page 179: ...This Page Intentionally Left Blank ...
Page 180: ...5 HANDLING I O DATA ON J NET ...
Page 186: ...6 HANDLING I O DATA ON D Station ...
Page 191: ...This Page Intentionally Left Blank ...
Page 192: ...7 MAINTENANCE ...