7. Wiring
7-21
Figure 7-19 Examples of connections between panels installed in a row
Panel 1
ST
Remote I/O cable
Connect the FG
terminal of the RI/O-IF
module to the FG
terminal of the power
supply module and the
FG terminal of the
mount base by using
daisy-chain wiring.
When implementing single-ended
grounding, do not connect the FG
terminal of the remote I/O station
module to the FG terminal of the
I/O mount base.
PS
RI/O
-IF
PS
FG terminal of the I/O
mount base
FG terminal of the
mount base
FG
terminal
Class D grounding with the ground
resistance of 100Ω or less for PCs
Ground point for PCs unit
FG terminal of the
power supply module
FG terminal
Panel 2