7. Wiring
7-24
7.9.2 Example of duct wiring
Figure 7-23 shows an example of ducting in a cabinet in which each duct carries cables for a different circuit
classification.
- Provide as much distance as possible between ducts for different circuit classifications.
- Where the ducts for different circuit classifications cross, have them cross at right angles.
- Avoid having HC or LC wiring run in parallel with LT or LS wiring.
If doing so is unavoidable, leave clearance of at least 200 mm between them.
Figure 7-23 Example of wiring ducts carrying cables for different circuit classifications
(top view)
Front
Rear
LT Area for wiring
external cables
inside the cabinet
LS
LC Area for wiring
external cables
inside the cabinet
HC Area for wiring
external cables
inside the cabinet
Duct
Duct
S10VE
Wiring duct at bottom of unit
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......