13. Troubleshooting
13-58
Table 13-28 Error codes reported to the CPU module from the ET.NET module (3/4)
No.
Error code
Error message
Description
ERR
LED
ALARM
LED
CPU module
indicator
display
Corrective action
35
0x500E7308
Module error (ET.NET
SEND_TIMEOUT)
ET.NET
transmission timeout
error
#1, #3
ON
--
0E7308
If recovery is not
possible even after
restoring power,
replace the module.
36
0x500E730A
Module error (ET.NET
RESET_ERROR)
ET.NET hard reset
error
#3
ON
--
0E730A
If recovery is not
possible even after
restoring power,
replace the module.
37
0x500E7505
Module error (ET.NET
INV_INTR)
ET.NET invalid
interrupt generated
from the line
#3
ON
--
0E7505
Replace the module.
38
0x500E7510
I/O error (ET.NET
IFCONFIG_UP)
ET.NET network
driver initialization
error
#3
--
ON
0E7510
Check and correct the
settings.
39
0x500E7511
I/O error (ET.NET
NETADDR_DUPL)
ET.NET duplicate
network address
error (system setup
setting error)
--
ON
0E7511
Check and correct the
network settings.
40
0x500E7512
I/O error (ET.NET
IPADDR_DUPL)
ET.NET duplicate
IP address error
(system setup setting
error detected on
startup)
#3
--
ON
0E7512
Check and correct the
IP address settings.
41
ET.NET duplicate
IP address error
(system setup setting
error detected when
online)
#3
--
--
0E7512
Check and correct the
IP address settings.
42
0x500E7D1C
I/O error (ET.NET Invalid
network setting)
ET.NET
communication
setting undefined
--
ON
0E7D1C
Specify the
communication
settings.
43
0x500E7D01
Module error (ET.NET
INVALID EXCEPTION)
ET.NET invalid
exception generated
ON
--
0E7D01
Replace the module.
44
0x500E7D11
Module error (ET.NET
Invalid MAC ADDRESS)
ET.NET MAC
address error
ON
--
0E7D11
Replace the module.
45
0x500E7D12
I/O error (ET.NET Invalid
MAIN/SUB switch setting
Duplication)
ET.NET duplicate
MAIN/SUB switch
setting
#5, #6
--
ON
0E7D12
Check and correct the
setting of the
MAIN/SUB setting
switch.
46
0x500E7D1A
I/O error (ET.NET Invalid
MAIN/SUB switch setting)
ET.NET
MAIN/SUB switch
setting error
#5
--
ON
0E7D1A
Check and correct the
setting of the
MAIN/SUB setting
switch.
47
0x500E7D1B
I/O error (ET.NET Invalid
ST. No. switch setting)
ET.NET ST.no.
switch setting error
#5
--
ON
0E7D1B
Check and correct the
setting of the ST.No.
setting switch.
48
0x500ED010
Module error (ET.NET
Memory Alarm)
ET.NET memory 1-
bit error (solid)
ON
--
0ED010
Replace the module.
49
0x500ED810
Module error (ET.NET
BPU Error)
ET.NET BPU error
ON
--
0ED810
Replace the module.
ON: On, --: Off
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......