14. Adding and Replacing Modules
14-12
14.4.3 Adding an OD.RING module
(1) Make a note of the information displayed on the indicator of the CPU module, and whether each of its
LEDs(RUN, ALARM, STBY, ERR) is on, off, or blinking.
(2) Slide the LADDER RUN/STOP switch on the CPU module from RUN to STOP, and confirm that
LDRSTP
appears on the indicator.
(3) Use the RAS menu in BASE SYSTEM/S10VE to save the CP and HP error log information for the CPU
module. For details on how to save this information, see
8.4.6.2 RAS menu: Error Log Display
.
(4) Slide the CPU RUN/STOP switch on the CPU module from RUN to STOP, and confirm that
CPUSTP
appears on the indicator.
(5) Turn off the power switch of the power supply module.
(6) Mount the OD.RING module to the mount base, and tighten the module fixing screws(M4) at the top
and bottom of the OD.RING module(tightening torque: 1.0 N
·
m).
(7) Set the MODU No. and CPL No. setting switches on the OD.RING module. For details on how to set
these switches, see the
S10VE User's Manual Option OD.RING (LQE510-E)
(manual number SEE-1-
101). Make sure that the setting of the MODU No. setting switch does not conflict with those of other
OD.RING modules.
(8) Turn on the power switch of the power supply module.
(9) Set the CPU RUN/STOP switch of the CPU module to RUN.
(10) Start BASE SYSTEM/S10VE, and set up the OD.RING module you added. For details on how to set up
a new OD.RING module, see the
S10VE User's Manual Option OD.RING (LQE510-E)
(manual number
SEE-1-101).
(11) Turn off the power switch of the power supply module.
(12) Remove the dust-proof caps attached to the optical fiber cables and the connectors of the OD.RING
module, and clean the connectors. Then, connect the optical fiber cables to the connectors on the
OD.RING module.
(13) Perform optical power measurement. For details on how to measure optical power, see
6.5 Measuring
optical power levels
in the
S10VE User's Manual Option OD.RING (LQE510-E)
(manual number SEE-
1-101).
(14) Turn on the power switch of the power supply module.
(15) Set the LADDER RUN/STOP switch on the CPU module to RUN.
(16) Confirm that the state of the LEDs on the OD.RING module is as follows:
TX LED: Blinking
RX LED: Blinking
ERR LED: Off
(17) Back up the data on the PCs. For details on how to back up the data on the PCs, see
14.11.1 Backup
procedure
.
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......