2. Overview
2-5
2.3 System components
2.3.1 Components of CPU unit
Table 2-1 shows the components that make up the CPU unit.
The specifications and functions of the mount base, power supply module, CPU module, and RI/O-IF module
are explained in the following chapters:
- Chapter 3: Specifications
- Chapter 5: Part Names and Functions
For details about the specifications and functions of the option modules, see the following manuals:
- S10VE User's Manual Option OD.RING (LQE510-E) (manual number SEE-1-101)
- S10VE User's Manual Option J.NET (LQE540-E) (manual number SEE-1-102)
- S10VE User's Manual Option D.NET (LQE770-E) (manual number SEE-1-103)
- S10VE User's Manual Option FL.NET (LQE702-E) (manual number SEE-1-104)
- S10VE User's Manual Option ET.NET (LQE260-E) (manual number SEE-1-105)
For details about the specifications and functions of the PI/O modules, see the following manual:
- S10mini Hardware Manual I/O Modules (manual number SME-1-114)
Table 2-1 List of CPU unit components (1/2)
No.
Name
Model
number
Description
1 Mount base
HSC-1770
- A 7-slot mount base for the S10VE.
- A maximum of seven modules (option modules and I/O modules) can be mounted
on the mount base. These include the power supply module, CPU module, RI/O-
IF module, option modules, and HSC-1000 PI/O modules.
2 Power supply
LQV410
- Input: 100 to 120 V AC, 100 to 110 V DC
- Output: 5 V DC, 10 A
3 CPU
LQP600
The CPU module for the S10VE.
4 RI/O-IF
LQE950
The remote I/O interface module.
5 ET.NET
LQE260-E
An option module for the S10VE that provides TCP/IP or UDP/IP protocol
communication that conforms to the IEEE802.3i (10BASE-T) or IEEE802.3u
(100BASE-TX) specification.
6 OD.RING
LQE510-E
A dedicated option module for the S10VE that allows data sharing through memory
transfer between CPU units.
For I/O data, the maximum size of shared data is 4,096 points. For word data, the
maximum size is 4,096 words.
7 FL.NET
LQE702-E
A dedicated option module for the S10VE that conforms to the FL-net standard.
FL-net is an open FA network that was standardized by the JEMA (Japan Electrical
Manufacturers' Association). It provides control and monitoring by enabling
interconnection of programmable controllers (PLC), personal computers, and other
FA devices produced by different manufacturers.
Summary of Contents for S10VE
Page 1: ...User s Manual General Description SEE 1 001 A ...
Page 2: ...User s Manual General Description ...
Page 53: ...This page is intentionally left blank ...
Page 59: ...This page is intentionally left blank ...
Page 67: ...This page is intentionally left blank ...
Page 75: ...This page is intentionally left blank ...
Page 77: ...This page is intentionally left blank ...
Page 103: ...This page is intentionally left blank ...
Page 129: ...This page is intentionally left blank ...
Page 295: ...This page is intentionally left blank ...
Page 309: ...This page is intentionally left blank ...
Page 341: ...This page is intentionally left blank ...
Page 345: ...This page is intentionally left blank ...
Page 475: ...This page is intentionally left blank ...
Page 489: ...This page is intentionally left blank ...
Page 505: ......