APPENDIX PARAMETER OBJECT LISTS
29
Function
Inst
Attr
Size
Monitoring/Setting Range
Magnifi-
cation
Access
rule
Com
mand
Digital Input 4 (Param219)
1
104
1
Same above
1
Get/Set
C004
Digital Input 5 (Param220)
1
105
1
Same above
1
Get/Set
C005
Digital Input 6 (Param221)
1
106
1
Same above
1
Get/Set
C006
Digital Input 7 (Param222)
1
107
1
Same above
1
Get/Set
C007
Digital Input 8 (Param223)
1
108
1
Same above
1
Get/Set
C008
Dig Input1 NO/NC (Param224)
1
111
1
00(NO)/01(NC)
1
Get/Set
C011
Dig Input2 NO/NC (Param225)
1
112
1
00(NO)/01(NC)
1
Get/Set
C012
Dig Input3 NO/NC (Param226)
1
113
1
00(NO)/01(NC)
1
Get/Set
C013
Dig Input4 NO/NC (Param227)
1
114
1
00(NO)/01(NC)
1
Get/Set
C014
Dig Input5 NO/NC (Param228)
1
115
1
00(NO)/01(NC)
1
Get/Set
C015
Dig Input6 NO/NC (Param229)
1
116
1
00(NO)/01(NC)
1
Get/Set
C016
Dig Input7 NO/NC (Param230)
1
117
1
00(NO)/01(NC)
1
Get/Set
C017
Dig Input8 NO/NC (Param231)
1
118
1
00(NO)/01(NC)
1
Get/Set
C018
FW NO/NC (Param232)
1
119
1
00(NO)/01(NC)
1
Get/Set
C019
Dig Output11 (Param233)
1
121
1
00(RUN)/01(FA1)/02(FA2)/03(OL)/
04(OD)/05(AL)/06(FA3)/07(OTQ)/
08(IP)/09(UV)/10(TRQ)/11(RNT)/
12(ONT)/13(THM)/19(BRK)/
20(BER)/21(ZS)/22(DSE)/23(POK)/
24(FA4)/25(FA5)/26(OL2)
(Intelligent output terminal 11 to 13
or 11 to 14 becomes AC0 to AC2 or
AC0 to AC3
(Can:Alarm cord output)forcibly
when alarm cord output is selected
in C062)
1
Get/Set
C021
Dig Output12 (Param234)
1
122
1
Same above
1
Get/Set
C022
Dig Output13 (Param235)
1
123
1
Same above
1
Get/Set
C023
Dig Output14 (Param236)
1
124
1
Same above
1
Get/Set
C024
Dig Output15 (Param237)
1
125
1
Same above
1
Get/Set
C025
AlarmRerayOutput (Param238)
1
126
1
Same above
1
Get/Set
C026
FM Mode Select (Param239)
1
127
1
00(Output Frequency)/
01(Output Current)/
02(Output Torque)/
03(Digital Outp-frq)/
04(Output Voltage)/
05(Input Power)/
06(Therm Load Rate)/
07LAD frequency)/
1
Get/Set
C027
AM Mode Select (Param240)
1
128
1
00(Output Frequency)/
01(Output Current)/
02(Output Torque)/
04(Output Voltage)/
05(Input Power)/
06(Therm Load Rate)/
07LAD frequency)/
1
Get/Set
C028
AMI Mode Select (Param241)
1
129
1
00(Output Frequency)/
01(Output Current)/
02(Output Torque)/
04(Output Voltage)/
05(Input Power)/
06(Therm Load Rate)/
07LAD frequency)/
1
Get/Set
C029
Dig Out11 NO/NC (Param242)
1
131
1
00(NO)/01(NC)
1
Get/Set
C031
Dig Out12 NO/NC (Param243)
1
132
1
00(NO)/01(NC)
1
Get/Set
C032
Dig Out13 NO/NC (Param244)
1
133
1
00(NO)/01(NC)
1
Get/Set
C033
Dig Out14 NO/NC (Param245)
1
134
1
00(NO)/01(NC)
1
Get/Set
C034
Dig Out15 NO/NC (Param246)
1
135
1
00(NO)/01(NC)
1
Get/Set
C035
AlarmReray NO/NC (Param247)
1
136
1
00(NO)/01(NC)
1
Get/Set
C036
OLAlarmSignalSel (Param248)
1
140
1
00(Valid)/01(Valid at const)
1
Get/Set
C040
OL Alarm Level 1 (Param249)
1
141
2
0 to 200(%) (constant current)
1
Get/Set
C041
ArrivalFreq Acc1 (Param250)
1
142
4
0.00 to 400.00(Hz)
100
Get/Set
C042
ArrivalFreq Dec1(Param251)
1
143
4
0.00 to 400.00(Hz)
100
Get/Set
C043
PID DeviationLvl (Param252)
1
144
2
0.0 to 100.0(%)
10
Get/Set
C044
ArrivalFreq Acc2 (Param253)
1
145
4
0.00 to 400.00(Hz)
100
Get/Set
C045
ArrivalFreq Dec2 (Param254)
1
146
4
0.00 to 400.00(Hz)
100
Get/Set
C046
OV-TRQ FW-V (Param255)
1
155
1
0 to 200(%)
1
Get/Set
C055
OV-TRQ RV-R (Param256)
1
156
1
0 to 200(%)
1
Get/Set
C056
OV-TRQ RV-V (Param257)
1
157
1
0 to 200(%)
1
Get/Set
C057
OV-TRQ FW-R (Param258)
1
158
1
0 to 200(%)
1
Get/Set
C058
Thermal Warn Lvl (Param259)
1
161
2
0 to 100(%)
1
Get/Set
C061
AlarmMode Select (Param260)
1
162
1
00(Invalid)/01(3bit)/02(4bit)
1
Get/Set
C062