8-3
Chapter 8
FAQ and Troubleshooting
8.3 Inverter troubleshooting
In case the some error was detected by the
inverter, it shuts the motor output down (trip).
When the trip occurs, the inverter display (VOP)
shows below.
The number of E005 in the above is an error code.
Abnormality related to this device and its solutions
are shown the following table.
■
Abnormality and its solutions.
For the list of errors issued by the inverter, that is
shown the following table. For more information
about those errors, refer to the inverter user's
guide.
Error display
Possible cause
Solutions
Abnormality
without
error code
The inverter cannot be powered on.
Troubleshoot according to the instructions
described in the inverter user's guide.
It may have been damaged that the
connector connecting this device to the
inverter.
Please exchange the device.
Allocated the function "Reset" to the
inverter input terminal, so when the
terminal may be turned on.
Verify the inverter parameters configuring.
[SLOT 1]
E060.*
E069.*
[SLOT 2]
E070.*
E079.*
[SLOT 3]
E080.*
E089.*
Fatal abnormality occurred in this device
when powered on or operating.
Turn off the inverter, then detach and attach
again this device. After this, turn on the
inverter again. In case the trouble cannot be
solved, please exchange the device.
It may have been damaged that the
connector connecting this device to the
inverter.
Please exchange the device.
This device is disconnected or not
connecting properly.
Make sure that this product and the inverter
are properly attached.
List
----
46.49Hz
oFW
TRIP
M1
H07
Occurring trip
Overload MTR
E005 15/12/24 22:10
Out Freq :0.50Hz
Current :49.71A
PN Voltage :274.1Vdc
Status1 :Stop
NRDY