6-6
Chapter 6
Inverter Settings
6.2.3
Inverter and P1-EN correlating
parameters
The parameters described in the following table
control the action taken by the inverter when there
is a problem with this device or when this device is
connected.
■
Parameter
・[oA-10]: Operation mode on option card
error (SLOT-1)
・[oA-20]: Operation mode on option card
error (SLOT-2)
・[oA-30]: Operation mode on option card
error (SLOT-3)
These parameters can select whether to ignore
the option error trip or not in cases where there
are connection failures between this device and
the inverter
Let the inverter trip: 00 (error)
Ignore the error and continue with the
operation: 01(Ignore error (keep running))
Please make sure to configure the parameter
corresponding to the slot in which this device is
attached.
In the event there is a communication failure
between the inverter and tis device, and the
option 01 (Ignore error (keep running)) is selected,
the inverter operation will not stop.
Additionally, in case there is a communication
failure between this device and the inverter, the
client (master) stop command will not be received.
Thus, safety measures and precautions are
recommended.
・[oA-13]: Run command selection at start
up (SLOT-1)
・[oA-23]: Run command selection at start
up (SLOT-2)
・[oA-23]: Run command selection at start
up (SLOT-3)
These parameters can select whether to execute
run commands or not while this device and the
inverter communication is being established
Do not execute: 00(run command disabled)
Execute: 01(run command enabled)
Please make sure to configure the parameter
corresponding to the slot in which this device is
attached.
This function can be used in cases when it is
required to operate the inverter as soon as it is
turned on. However, since the inverter will operate
before the communication is established, we
recommend taking precautions accordingly, when
designing the system.
Code
Parameter name
Selection
Initial value
oA-10
Operation mode on option card
error (SLOT-1)
00(Error)/
01(Ignore error (keep running))
00
oA-13
Run command selection at start up
(SLOT-1)
00(run command disabled)/
01(run command enabled)
00
oA-20
Operation mode on option card
error (SLOT-2)
00(Error)/
01(Ignore error (keep running))
00
oA-23
Run command selection at start up
(SLOT-2)
00(run command disabled)/
01(run command enabled)
00
oA-30
Operation mode on option card
error (SLOT-3)
00(Error)/
01(Ignore error (keep running))
00
oA-33
Run command selection at start up
(SLOT-3)
00(run command disabled)/
01(run command enabled)
00
!
!
Summary of Contents for SJ-P1 Series
Page 9: ...C 3 Table of Contents Memo ...
Page 17: ...1 8 Chapter 1 Safety Precautions Memo ...
Page 21: ...2 4 Chapter 2 Overview Memo ...
Page 25: ...3 4 Chapter 3 About the P1 EN Memo ...
Page 29: ...4 4 Chapter 4 Enclosed Items Memo ...
Page 45: ...6 8 Chapter 6 Inverter Settings Memo ...