Example Wiring Diagram
Oper
ations
and Monitor
ing
4–6
Specifications of Control and Logic Connections
The control logic connectors are located just behind the front panel half-door. The relay
contacts are accessible behind the main door. Connector labeling is shown below.
Specifications for the logic connection terminals are in the following table:
Note 1:
The two terminals [L] are electrically connected together inside the inverter.
Relay
contacts
Logic
inputs
Analog
inputs
Analog
output
Logic
outputs
12 11
1
2
3
4
5
6
L
L
H O OI
FM CM2
P24
AL0
AL2
AL1
Terminal Name
Description
Ratings
[P24]
+24V for logic inputs
24VDC, 30 mA max (do not short to terminal L)
[1], [2], [3], [4], [5],
[6]
Discrete logic inputs
27VDC max. (use P24 or an external supply refer-
enced to terminal L)
[L] (top row) *1
GND for logic inputs
sum of input 1-6 currents (return)
[11], [12]
Discrete logic outputs
50mA maximum ON state current,
27 VDC maximum OFF state voltage
[CM2]
GND for logic outputs
100 mA: sum of 11 and 12 currents (return)
[FM]
PWM (analog/digital) output 0 to 10VDC, 1 mA, PWM and 50% duty digital
[L] (bottom row) *1 GND for analog inputs
sum of OI, O, and H currents (return)
[OI]
Analog input, current
4 to 19.6 mA range, 20 mA nominal
[O]
Analog input, voltage
0 to 9.6 VDC range, 10VDC nominal,
input impedance 10 k
Ω
[H]
+10V analog reference
10VDC nominal, 10 mA max
[AL0]
Relay common contact
250 VAC, 2.5A (R load) max.,
250 VAC, 0.2A (I load, P.F.=0.4) max.
100 VAC, 10mA min.
30 VDC, 3.0A (R load) max.
30 VDC, 0.7A (I load, P.F.=0.4) max.
5 VDC, 100mA min.
[AL1]
Relay contact, normally
closed during RUN
[AL2]
Relay contact, normally open
during RUN