![background image](http://html.mh-extra.com/html/hitachi/sj100dn-devicenet-series-addendum/sj100dn-devicenet-series-addendum_instruction-manual_142350088.webp)
SJ100DN Inverter
87
Intelligent Terminal Functions
“C” Group Parameters
DeviceNet Class ID = 105
Func.
Code
Name
Inst Attr Size
Range
Scaling
Get/
Set
C_01 Terminal [1] function
1
101
1
0, 1, 2, 3, 4, 5, 6, 7,
8, 9, 11, 12, 13,
15, 18, 19, 20, 21,
22, 25, 27, 28, 31
(see manual,
Chapter 3)
—
G/S
C_02 Terminal [2] function
1
102
1
(same as above)
—
G/S
C_03 Terminal [3] function
1
103
1
(same as above)
—
G/S
C_11 Terminal [1] active state
1
111
1
0 normally open
1 normally closed
—
G/S
C_12 Terminal [2] active state
1
112
1
0 normally open
1 normally closed
—
G/S
C_13 Terminal [3] active state
1
113
1
0 normally open
1 normally closed
—
G/S
C_21 Terminal [11] function
1
121
1
0, 1, 2, 3, 5 (see
manual, Ch. 3)
—
G/S
C_22 Terminal [12] function
1
122
1
(same as above)
—
G/S
C_31 Terminal [11] active state
1
131
1
0 normally open
1 normally closed
—
G/S
C_32 Terminal [12] active state
1
132
1
0 normally open
1 normally closed
—
G/S
C_41 Overload level setting
1
141
2
0% to 200% rated
current, in A
100
G/S
C_42 Frequency arrival setting for
accel
1
142
2
0.0 – 360.0Hz
100
G/S
C_43 Arrival frequency setting for
decel
1
143
2
0.0 – 360.0Hz
100
G/S
Supported Services, DeviceNet Class ID = 105
Service Name
Code
Description
Get_Attribute_Single
0Eh
Set_Attribute_Single
10h
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com