CHAPTER4 SETTING
10
4.2 Parameter setting of the Inverter
Following table describes setting items relate SJ200-2/L200-2 series Inverter with connecting SJ2-CO.
Following parameter will appear with connecting SJ2-CO to SJ200-2/L200-2 Inverter.
Parameter
Function
Range of DATA
Initial
DATA
Note
P044
Timer setting of
Communication
timeout Whilst
running
0.00~99.99
0.00
**
P045
Inverter action
when
communication
error
00(TRIP) / 01(TRIP after
deceleration stop)
/ 02(ignore) / 03(Free-RUN)
/ 04(deceleration stop)
01
It is effective when
“Object #6007”
setting is ‘-3’.
P049*
Motor Poles
setting for
revolution per
minutes
0 to 38
(It is possible to set only even
number )
Setting value ‘0’, monitoring unit is
Hz.
Setting value except ‘0’, monitoring
unit is min
-1
.
0
Note*: As “P049 Command” value is setting ‘0’, unit of “Index 6042,6043,6044,6046,6048-1,6049-1”
is ‘Hz’.
Note**: CANopen Interface Option cannot detect bus-off status with heartbeat. Using P045 command,
set value of P044 instead of detecting bus-off status.
4.3 Power Supply LED check
If the Power Supply LED(See 1.3) is not ON ,please remount(See 2.1) the SJ2-CO unit again.