SJ300 Inverter

Derating Curves

The maximum available inverter current output is limited by the carrier frequency and ambient 
temperature. The carrier frequency is the inverter’s internal power switching frequency, settable 
from 0.5 kHz to 12 kHz. Choosing a higher carrier frequency tends to decrease audible noise, 
but it also increases the internal heating of the inverter, thus decreasing (derating) the maximum 
current output capability. Ambient temperature is the temperature just outside the inverter 
housing—such as inside the control cabinet where the inverter is mounted. A higher ambient 
temperature decreases (derates) the inverter’s maximum current output capacity.

Use the following derating curves to help determine the optimal carrier frequency setting for 
your inverter, and to find the output current derating. Be sure to use the proper curve for your 
particular SJ300 inverter model number.

SJ300 1.5 to 22 kW at 50 deg. C ambient

2

4

6

8

10

12

14 15

0.5

65%

70%

75%

80%

85%

90%

95%

100%

Carrier Frequency (kHz)

%

 of Driv

e’

s Rated Amps

004 to 150L

185L

220L

SJ300 30 to 55 kW at 50 deg. C ambient

2

4

6

8

10

12

14 15

0.5

65%

70%

75%

80%

85%

90%

95%

100%

Carrier Frequency (kHz)

% of Dri

ve’

s Rated

 Amp

s

370L

300L

450L

550L

450L

550L

Summary of Contents for SJ300 Series

Page 1: ...0 at 0 Hz with feedback board Dynamic braking approx torque short time stop 7 internal res only 50 20 10 with external res 200 160 100 80 70 DC braking Variable operating frequency time and braking force Weight kg lb 3 5 7 7 3 5 7 7 3 5 7 7 3 5 7 7 3 5 7 7 3 5 7 7 5 11 5 11 Item 200V Class Specifications continued SJ300 inverters 200V models UL version 150LFU 185LFU 220LFU 300LFU 370LFU 450LFU 550...

Page 2: ...raking approx torque short time stop 7 internal res only 50 20 10 with external res 200 140 100 70 DC braking Variable operating frequency time and braking force Weight kg lb 3 5 7 7 3 5 7 7 3 5 7 7 3 5 7 7 3 5 7 7 55 121 55 121 Item 400V Class Specifications SJ300 inverters 400V models UL version 150HFU 185HFU 220HFU 300HFU 370HFU 450HFU 550HFU CE version 150HFE 185HFE 220HFE 300HFE 370HFE 450HFE...

Page 3: ...oltage 0 to 10 VDC or at 19 6 mA for input current 4 to 20 mA If this characteristic is not satisfactory for your application contact your Hitachi sales representative Note 9 The storage temperature refers to the short term temperature during transport Note 10 Conforms to the test method specified in JIS C0911 1984 For the model types excluded in the standard specifications contact your Hitachi sa...

Page 4: ... SET3 set 3rd motor data RS reset inverter STA start 3 wire interface STP stop 3 wire interface F R FW RV 3 wire interface PID PID ON OFF PIDC PID reset CAS control gain setting UP remote control Up function motorized speed pot DWN remote control Down function motorized speed pot UDC remote control data clearing OPE Operator control SF1 SF7 Multispeed bits 0 7 OLR Overload limit change TL torque l...

Page 5: ... error external trip USP error ground fault input over voltage instantaneous power failure expansion card 1 error expansion card 2 error inverter thermal trip phase failure detection IGBT error thermistor error Environ ment Temperature 9 Operating ambient 10 to 50 C Storage 20 to 65 C Humidity 20 to 90 humidity non condensing Vibration 10 Models SJ300 004xxx to 220xxx 5 9 m s2 0 6G 10 to 55 Hz Mod...

Page 6: ...ing such as inside the control cabinet where the inverter is mounted A higher ambient temperature decreases derates the inverter s maximum current output capacity Use the following derating curves to help determine the optimal carrier frequency setting for your inverter and to find the output current derating Be sure to use the proper curve for your particular SJ300 inverter model number SJ300 1 5...

Page 7: ...5 100 Carrier Frequency kHz of Drive s Rated Amps 370H 450H 300H 550H SJ300 30 to 55 kW at 50 deg C ambient continued SJ300 75 to 150 kW at 50 deg C ambient 2 4 6 8 10 12 14 15 0 5 65 70 75 80 85 90 95 100 Carrier Frequency kHz of Drive s Rated Amps 750H 900H 1100H 1320H 1500H 60 220H 60 015 to 185H ...

Reviews: