background image

4

13. Now, click on the CONTROL TYPE menu key and select which type is appropriate for your application.  The

DEADBAND CONTROL is an on/off control and PID CONTROL is a proportional/integral/derivative control.  The
COMPUTER CONTROL acts like an electronic variac in that a fixed percentage of power may be applied to the load.

14. Clicking on the CONTROL MODE menu key permits the selection of either HEAT WP1+ and WP2- or HEAT WP2+

and WP1-.  This selection establishes the polarity for the heating mode of the thermoelectric module.  (i.e. If the
positive side of the module is connected to WP1 and the negative side to WP2, the module will heat when power is
applied to the module, and vice versa if the wiring is reversed.)  This selection allows you to reverse the current flow
in the thermoelectric module without changing the wiring.

15. The ALARM TYPE setting permits the selection of available alarm options with this controller.  The drop down

menu allows for four selections.  NO ALARM PICKED indicates that no alarm parameters are desired.  SET
TRACKING ALARMS allows an alarm to be set with respect to the set temperature and will move, accordingly, with
a change of the temperature setting.  This option can be used for a high alarm, low alarm, or both settings.  FIXED
VALUE ALARMS permits the setting of a fixed, absolute temperature either above or below the set point temperature
or both.  COMPUTER CONTROLLED ALARM is not an actual alarm, but a user activation of the alarm relay via the
PC.

16. The POWER OUT SHUT DOWN IF ALARM menu key provides two selections. NO SHUT DOWN IF ALARM

which will let the power output stage of the controller to continue to function or MAIN OUT SHUTDOWN IF
ALARM which disables the power output stage under an alarm condition.

17. Associated with the ALARM TYPE configuration are the HIGH ALARM SETTING, LOW ALARM SETTING, and

the ALARM DEADBAND selections.  If an alarm type has been selected, enter the desired high and low temperature
values.  The ALARM DEADBAND option is to set the hysteresis of the alarm values from 0.1°F. to 100°F.

18. The ALARM LATCH option permits the selection of an ALARM LATCH OFF where the controller will automatically

reset if the alarm condition is self-correcting or ALARM LATCH ON which will maintain that an alarm condition
existed and must be manually cleared.

19. The CHOOSE SENSOR FOR ALARM option allows for the selection of either the thermistor CONTROL SENSOR or

the INPUT 2 SENSOR be used for the alarm.

20. The CHOOSE DEG C OR DEG F menu key permits the selection of displaying DEG F or DEG C.

21. Review all of your controller configuration selections.  If all the configuration selections are correct for your

application, select the Send Box Values button to download these settings to the controller.

22. You are now ready to tune the controller.  All selections for this portion will occur in the menu tree TUNING box

displayed on the monitor.

23. The various constants required by the controller to optimize the system performance are entered in this section.

11

TC

-1

36

TS

67

 a

t -

2

C

 t

o

 1

0

C

TS

14

at

 -

40

°C

 t

o

 7

C

Summary of Contents for TC-136

Page 1: ...ERMOELECTRIC MODULE TEMPERATURE CONTROLLER HiTECH Technologies Inc 301 Oxford Valley Road Yardley PA 19067 7706 Tel 215 321 6012 Fax 215 321 6067 Technical support 800 755 4507 or 888 NIVELCO Email in...

Page 2: ...NOTES 16...

Page 3: ...als are expressed in repeats minute The acceptable range for the TC 136 is 0 01 to 10 repeats minute Start with a setting determined by the following formula Integral Reset 1 2 period Note Period is e...

Page 4: ...atisfactorily with only the P and I values used Start the tuning process by setting the Integral and Derivative functions to zero Proportional Bandwidth is defined as the temperature range around the...

Page 5: ...zontal or vertical orientation Input and output connections are accessible via screw type terminal strips fast on terminals and a 100 center connector TECHNICAL DESCRIPTION Model TC 136 is capable of...

Page 6: ...rm condition or the main power may be shut down 3 24 NOTE Refer to the Menu Tree in this manual for the factory default settings for the following parameters 25 The FIXED SET TEMP is the set temperatu...

Page 7: ...user activation of the alarm relay via the PC 16 The POWER OUT SHUT DOWN IF ALARM menu key provides two selections NO SHUT DOWN IF ALARM which will let the power output stage of the controller to con...

Page 8: ...r PC monitor 7 NOTE If you receive an error message please refer to Appendix A 8 All selections are made from this menu screen In the PC COMMUNICATIONS box select the COMM PORT 1 through 4 which will...

Page 9: ...TROL PID CONTROL COMPUTER CONTROL HEAT WP1 AND WP2 HEAT WP2 AND WP1 NO ALARMS PICKED SET TRACKING ALARMS FIXED VALUE ALARMS COMPUTER CONTROLLED NO SHUTDOWN IF ALARM MAIN OUT SHUTDOWN IF ALAR CONTROL S...

Page 10: ...7 8 CUSTOMER HOOK UP DRAWING EXPANSION CONNECTOR WIRING DIAGRAM TC 136...

Reviews: