10
05.17 207646 Rev.103
EKWXA│EKWXBA
AIR-COOLED WATER CHILLERS
AXIAL FANS
RECEPTION
INSPECTION
At the time of equipment delivery it is advisable to examine it carefully.
Check that the equipment has not been damaged during transport and has been supplied complete with all parts specified in the
order and/or with the optionals specified in the order. If this is not the case contact the transport company immediately. (First 48h).
Verify the correct voltage of the nameplate and make sure it’s in accordance with local power supply.
In case of any flaw or anomaly detected, please contact HITECSA.
RIGGING
Before moving the unit, make sure that all panels are well fixed.
Raise and set down the equipment carefully.
Do not tilt the unit more than 15 degrees during transportation.
When lifting the unit, make sure that it’s balanced and stable; bear in mind that the heaviest part is where the compressor is installed.
Always transport the unit in its original packaging to the place of installation.
Lifting through crane.
STORAGE
If the equipment is going to be stored please follow the instructions below in order to avoid damages, corrosion or deterioration:
Do not place the machine in places exposed to ambient temperature above 50ºC and preferably keep the unit away from direct
sunlight.
Avoid prolonged storage, before installation, water inlet, dust and objects in general due to invasion or biological, meteorological
and/or human inclemencies.
Minimum storage temperature is 5ºC.
Maximum Relative Humidity: 90%.
It is also recommended:
Move it carefully.
Avoid placing other objects on top of the unit (unless it is done within the limits of the overlap planes indicated on the packaging).
Avoid placing the unit with heat-shrink protection under the sun, as the pressure of the circuits could assume values that could lead
to the intervention of the safety valves.