HR-10 Series 

   

        HITROL CO., LTD.                                                                                6 

 

Please do not move the stopper holding the float at random.

 

Wiring 

The  terminals of the products are composed according to contact points and shall be 

connected as follows. 

 

 

HR-10S (PA66) 

1 : E1 

2 : E2 

3 : Com 

G : Ground

 

 

 

 

 

 

 

 

 

HR-10S (AL) 

  A : E1 

          B : E2 

          C : Com 

 

 

 

 

 

 

 

 

                 

HR-10T (P.C) 

Com : Com 

E1 : E1

 

 

 
Matters 
Regarding 
Operation  and 
Use 

The product can be manufactured to N.O (Contact with A)/N.C (Contact with B) on orders 

from customers, and if there are no specific requirements for them, it can be manufactured to 

N.O (Contact with A). The shape of the contacts is shown below. 

 

 

 

 

 

 

Contact A (OFF) 

 

Contact A (ON) 

 

Contact B (OFF) 

 

Contact B (ON) 

NO

 

□NC 

 

 

□NO 

NC

 

Switch  ON,  when  the  level 

rises. (Contact with A)

 

Switch  ON,  when  the  level 

drops. (Contact with B)

 

Summary of Contents for HR-10 Series

Page 1: ...v 1 Issue date 2022 02 HITROL CO LTD HEAD OFFICE FACTORY R D INSTITUDE HITROL CO LTD 141 Palhakgol gil Jori eup Paju si Gyeonggi do Korea TEL 00 82 31 950 9700 FAX 00 82 31 943 5600 www hitrol com INSTRUCTION MANUAL FLOAT TYPE LEVEL SWITCH HR 10 Series ...

Page 2: ...med of the contents where WARNING is marked before carrying out the work Table of contents Overview 3 Operating Principle 3 Characteristics 3 Specifications 4 Minimum Section Distance 4 Dimensions 5 Wiring 6 Matters Regarding Operating and Use 6 Maintenance 7 Precautions for Removal 7 Precautions for Installation 7 Safety and Environment 8 Marking 8 User Training 8 Warranty and Contact 8 ...

Page 3: ...nk the float which is manufactured in accordance with the specific gravity of liquid moves upward or downward along the guide pipe with the same liquid level by buoyancy The built in magnet in the float activates reed switch which is located in the guide pipe and contact signal is out Each alarm or H L control with multiple setting points is available Characteristics Widely used to measure various...

Page 4: ... PG7 Std PF 3 4 F Std Contact From SPST SPDT SPST Max Contact From 1 SPST 2 SPST 1 SPDT 1 SPST Contact Rating 24VDC 0 5A 10W SPST 24VDC 0 25A 5W SPDT 24VDC 0 28A 10W SPST Minimum Section Distance Standard Type Float Size 1 Section A mm 40 Section B mm 55 Section C mm 40 100 A Upper Dead Band Minimum length which cannot be measured from the bottom of flange B Minimum distance between two setting po...

Page 5: ...HR 10 Series HITROL CO LTD 5 Dimensions WEATHER PROOF Version HR 10S 1F PA66 HR 10S 1F AL HR 10T P C HR 10S 2F PA66 HR 10S 2F AL ...

Page 6: ...C Com HR 10T P C Com Com E1 E1 Matters Regarding Operation and Use The product can be manufactured to N O Contact with A N C Contact with B on orders from customers and if there are no specific requirements for them it can be manufactured to N O Contact with A The shape of the contacts is shown below Contact A OFF Contact A ON Contact B OFF Contact B ON NO NC NO NC Switch ON when the level rises C...

Page 7: ...terminal blocks E1 E2 or N O N C and the COM terminal If the buzzer rings when the float reaches the upper lower contact points it works normally If the contact state is checked by resistance the Digital Multimeter indicates 0Ω by moving the float it is normal to the N C Normal Close and the N O Normal Open indicates infinite Precautions for Removal Check the level and presence of measurements in ...

Page 8: ...erature working pressure and matters regarding output The serial number is a unique manufacturing number for the identification of products User Training The fluid temperature of the container shall be up to 80 for Weather proof type In addition make sure that the ambient temperature of housing is kept at 20 60 However product with PVC sensor part the fluid temperature of the container is limited ...

Reviews: