The chimney conveying the boiler's exhaust must satisfy all the applicable standards,
requirements and the principles of construction.
Fig. 5. Placement of the Smart Fire boiler in the boiler room
8.3. Boiler's installation
Returning water cooled down below condensation point will result in accelerated corrosion.
The heating system must feature the necessary thermal protection to avoid that. Failure in
submission will nullify warranty!
The temperature of the returning water must not fall below 50
0
C. This condition must be satisfied
for performance of the warranty obligations and for the proper performance of the boiler. To
facilitate that you may apply either a for-way mixing valve with an attenuator or a thermostatic
valve set for 45ºC.
The installation must comply with the regulations in force, the industry standards and the
construction principles. Follow the installation sketches on the fig.6 below. Other, viable from the
Instrukcja Smart Fire
wer. 07/05/2010/ENG
HKS LAZAR
str.17