Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
M
L
L
E
D
7000 x c (100 x sa)
+ 3
x
x
x
R
Ballast / Lamp Failure bit fields
(ECG63-ECG48)
0-OK, 1-Ballast / Lamp Failure b
i
[
i
= sa - (16 * (line-1))]
7000 x c (100 x sa)
+ 4
x
x
x
R/W Update All ECG Status
0-Update Finished, 1-Trigger Update
7000 x c (100 x sa)
+ 5
x
x
x
R
Ballast Status
b7-PwrCycle, b6-MissShAdd, b5-ResetSt, b4-FadeRun,
b3-BallLimErr, b2-LampPwrOn, b1-LampFail, b0-BallFail
7000 x c (100 x sa)
+ 6
x
x
x
R
Actual Level
0 to 100 %
7000 x c (100 x sa)
+ 7
x
x
x
R
Device Type
0-Fluorescent, 1-Emergency, 2 Discharge, 3-Halogen, 4-
Incandescent, 5-Digital signal, 6-LED, 7-Switching, 8-
Colour Control
7000 x c (100 x sa)
+ 8
x
x
x
R
Physical Minimum Level
0 to 100 %
7000 x c (100 x sa)
+ 9
x
x
x
R
Min Level
0 to 100 %
7000 x c (100 x sa)
+ 10
x
x
x
R
Max Level
0 to 100 %
7000 x c (100 x sa)
+ 11
x
x
x
R
Power On Level
0 to 100 %
7000 x c (100 x sa)
+ 12
x
x
x
R
System Failure Level
0 to 100 %
7000 x c (100 x sa)
+ 13
x
x
x
R
Fade Time
0 to 15
7000 x c (100 x sa)
+ 14
x
x
x
R
Fade Rate
1 to 15
7000 x c (100 x sa)
+ 15
x
x
x
R/W Arc Power Level
0 to 100 %