Intesis
TM
Modbus Server
– DALI
User Manual r1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
19 / 39
Modbus Address
First Address is 0
Ballast /
Device type
Read/
Write
Register/signal name
Possible values
FL
E
ML
L
E
D
7000 * line + (20 * gr) + 6414
x
R/W Burn-in time Status
0-Stopped, 1-Running
7000 * line + (20 * gr) + 6415
x
R/W Burn-in time
0-Stop, 1-Start
2.4.3 Broadcast signals
Broadcast signals allow to control all ballasts in the same line from an individual signal. Their Modbus addresses can be obtained applying the following formula:
Modbus Address = 7000 x c SIGNAL NUMBER
Where:
LINE NUMBER;
0..1 (always 0 if using version with support for 1 DALI channel)
SIGNAL NUMBER:
6800..6815, see following table
Modbus address from the formula is expressed in link layer format. This is, first register address is 0.
Supported signals vary according to device type. Following abbreviations are done in the table:
•
FL: Fluorescent light (device type 0)
•
EML: Emergency light (device type 1)
•
LED: LED module (device type 6)