Status and Diagnostics 7-2
© 2012 HMS Industrial Networks AB
Doc.Id. HMSI-168-25
J1939 Status LED
Modbus Status LED
State
Summary
Description
Flashing Green
Initializing /
Offline
The J1939 network interface is cur-
rently being initialized and is waiting
to come online. The module is not par-
ticipating in J1939 traffic.
Solid Green
Online
A J1939 network address has been suc-
cessfully claimed and the module is
online and active.
Flashing Red/Green
Online with
Faults
The module is online and active on the
J1939 network, but faults have been
detected. Check the J1939 status codes
to determine the cause of the fault.
Solid Red
Offline
The module is not participating in the
J1939 network.
Flashing Red
Offline with
Faults
The module is not participating in the
J1939 network and faults have been
detected. Check the J1939 status codes
to determine the cause of the fault.
Table 7-2 J1939 Status LED States
State
Summary
Description
Flashing Green
Waiting
The Modbus interface is initialized and
waiting for requests from a Modbus
master.
Solid Green
Connected
The Modbus interface is actively pro-
cessing requests from a Modbus mas-
ter.
Table 7-3 Modbus Status LED States