3.6. I/O-Data Cycle Time Considerations
Based on recommendations from industrial equipment suppliers, such as Rockwell and Siemens, use the
following minimum I/Odata cycle times for PROFINET and EtherNet/IP networks:
• Wireless link Point-to-Point with Bluetooth PANU-PANU or Wi-Fi Access Point to Station: 32 ms
• Wireless link with Access Point and up to 4 wireless clients/stations, Bluetooth or Wi-Fi: 64 ms