Intesis
TM
KNX
– HISENSE VRF
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
24 / 30
8
Error codes for Indoor and Outdoor Units
This list contains all possible values shown in KNX Object for “Error Code” for each indoor unit and outdoor unit.
It must be taken into account that Outdoor Units are only able to reflect a single error for each indoor / outdoor unit in
the system. Thus, a unit having two or more active errors from that list will only report a single error code
– the one of
the first error that has been detected.
Error
Code
Category
Content of Abnormality
Leading Cause
01
lndoor Unit
Activation of Protection Device (Float
Switch)
Activation of Float Switch
(High Water Level in Drain Pan
,
Abnormality of Drain Pipe
,
Float Switch or
Drain Pan)
02
Outdoor Unit
Activation of Protection
Device (High Pressure
Cut)
Activation of PSH (Pipe
Clogging
,
Excessive Refrigerant!
lnert Gas Mixing)
03
Transmission
Abnormality between lndoor and
Outdoor
incorrect Wiring
,
Loose Terminals
,
Disconnect Wire
,
Blowout of Fuse
,
Outdoor Unit Power OFF
04
Abnormality between lnverter PCB
and Outdoor PCB
lnverter PCB - Outdoor PCB
Transmission Failure (Loose Connector
,
Wire Breaking
,
Blowout of Fuse)
04.
Abnormality between Fan Controller
and Outdoor PCB
Fan Controller - Outdoor PCB
Transmission Failure (Loose Connector
,
Wire Breaking
,
Blowout of Fuse)
05
Supply Phase
Abnormality Power Source Phases
lncorrect Power Source
,
Connection to Reversed
Phase
,
Open-Phase
06
Voltage
Abnormal lnverter
Voltage
Outdoor Voltage Drop
,
insufficient Power
Capacity
06.
Abnormal Fan Controller
Voltage
Outdoor Voltage Drop
,
lnsufficient Power
Capacity
07
Cycle
Decrease in Discharge Gas Superheat
Excessive Refrigerant! Charge
,
Failure
of Thermistor
,
lncorrect Wiring
,
lncorrect Piping Connection
,
Expansion
Valve Locking at Opened Position
(Disconnect Connector)
08
lncrease in Discharge Gas
Temperature
lnsufficient Refrigerant! Charge
,
Pipe Clogging, Failure of
Thermistor
,
lncorrect Wiring
,
lncorrect Piping Connection
,
Expansion
Valve Locking at Closed Position
(Disconnect Connector)
0A
Transmission
Abnormality between Outdoor and
Outdoor
lncorrect Wiring
,
Breaking Wire
,
Loose
Terminals
0b
Outdoor Unit
lncorrect Outdoor Unit Address
Setting
Duplication of Address Setting for
Outdoor Units (Sub Units) in Same
Refrigerant! Cycle System
0c
lncorrect Outdoor Unit Main Unit
Two (or more) Outdoor Units Set