Intesis
TM
KNX
– HISENSE VRF
User Manual r1.1 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
27 / 30
9
Appendix A – Communication Objects Table
TOPIC
NAME
LEN
DATAPOINT TYPE
FLAGS
FUNCTION
DPT_NAME
DPT_ID
R
W
T
U
GLOBAL
SIGNALS
ON/OFF
On/Off (all units)
1 bit
DPT_Switch
1.001
W
0-Off, 1-On
OP MODE
Operating Mode (all units)
1 byte
DPT_HVACContrMode
20.105
W
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry
Operating Mode (all units)
1 byte
Non-standarized
5.x
W
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
FAN SPEED
Fan Speed (all units)
1 byte
Non-standarized
5.x
W
1-Low, 2-Mid, 3-High, 4-High+
Fan Speed AUTO (all units)
1 bit
DPT_Switch
1.001
W
1-Set auto fan; 0-Stop auto fan
VANE POSITION
Vane position (all units)
1 byte
Non-standarized
5.x
W
1-Position 1...7-Position 7
Vane position AUTO (all units)
1 bit
DPT_Switch
1.001
W
1-Set auto vane; 0-Stop auto vane
SETP TEMP
Temperature Setpoint (ºC) (all units)
2 byte
DPT_Value_Temp
9.001
W
Cool:19..30 ºC; Heat:17..30 ºC
OUTDOOR
UNIT
SIGNALS
COMM ERROR
Status_Communication Error OU
1 bit
DPT_Alarm
1.005
R
T
0-No error, 1-Error
TEMPERATURES
Status_Outdoor Air Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
-50..99 ºC
Status_Compresor Top Temperature (ºC)
2 byte
DPT_Value_Temp
9.001
R
T
0..200 ºC
COMPRESOR
Status_Total Real Compresor Freq.
4 byte
DPT_Value_Frequency
14.033
R
T
0..255 Hz
Status_Total Compresor Current
4 byte
DPT_Value_Electric_Current
14.019
R
T
0..255 A
VALVE
Status_Out Exp. Valve 1 Open
1 byte
DPT_Scaling
5.001
R
T
0..100 %
PRESSURE
Status_Discharge Pressure
4 byte
DPT_Value_Pressure
14.058
R
T
-5.0..9.9 Mpa
Status_Suction Pressure
4 byte
DPT_Value_Pressure
14.058
R
T
-5.0..9.9 Mpa
ON / OFF
Control _On/Off
1 bit
DPT_Switch
1.001
W
0-Off,1-On
Status _On/Off
1 bit
DPT_Switch
1.001
R
T
0-Off,1-On
OP MODE
Control _Operation mode
1 byte
DPT_HVACContrMode
20.105
W
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry
Status _Operation mode
1 byte
DPT_HVACContrMode
20.105
R
T
0-Auto, 1-Heat, 3-Cool, 9-Fan, 14-Dry
Control _Operation mode
1 byte
Non-standarized
5.x
W
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
Status _Operation mode
1 byte
Non-standarized
5.x
R
T
0-Auto, 1-Heat, 2-Dry, 3-Fan, 4-Cool
Control _Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
W
0-Cool, 1-Heat
Status _Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
R
T
0-Cool, 1-Heat
Control _Heat mode&ON
1 byte
DPT_Scaling
5.001
W
0%-Off, 1%-100%-On+Heat