INDOOR UNIT
SIGNALS
Control _Cool mode&ON
1 byte
DPT_Scaling
5.001
W
0%-Off, 1%-100%-On+Cool
Control _Auto mode
1 bit
DPT_Switch
1.001
W
1-Set auto mode
Status _Auto mode
1 bit
DPT_Switch
1.001
R
T
1-Auto mode active, 0-Auto mode not active
Control _Heat mode
1 bit
DPT_Switch
1.001
W
1-Set heat mode
Status _Heat mode
1 bit
DPT_Switch
1.001
R
T
1-Heat mode active, 0-Heat mode not active
Control _Cool mode
1 bit
DPT_Switch
1.001
W
1-Set cool mode
Status _Cool mode
1 bit
DPT_Switch
1.001
R
T
1-Cool mode active, 0-Cool mode not active
Control _Fan mode
1 bit
DPT_Switch
1.001
W
1-Set fan mode
Status _Fan mode
1 bit
DPT_Switch
1.001
R
T
1-Fan mode active, 0-Fan mode not active
Control _Dry mode
1 bit
DPT_Switch
1.001
W
1-Set dry mode
Status _Dry mode
1 bit
DPT_Switch
1.001
R
T
1-Dry mode active, 0-Dry mode not active
Control_Fan speed enumerated
1 byte
Non-standarized
5.x
W
1-Low, 2-Mid, 3-High, 4-High+
FAN SPEED
Status _Fan speed enumerated
1 byte
Non-standarized
5.x
R
T
1-Low, 2-Mid, 3-High, 4-High+
Control _Fan speed scaling
1 byte
DPT_Scaling
5.001
W
Thersholds (0%..37%; 38%..62%; 63%..87%;
88%..100%)
Status _Fan speed scaling
1 byte
DPT_Scaling
5.001
R
T
Thersholds (25%; 50%; 75%; 100%)
Control_ Fan speed low
1 bit
DPT_Switch
1.001
W
1-Set fan speed low
Status_Fan speed low
1 bit
DPT_Switch
1.001
R
T
1-Speed low active, 0-Speed low not active
Control_Fan speed mid
1 bit
DPT_Switch
1.001
W
1-Set fan speed mid
Status_Fan speed mid
1 bit
DPT_Switch
1.001
R
T
1-Speed mid active, 0-Speed mid not active
Control_Fan speed high
1 bit
DPT_Switch
1.001
W
1-Set fan speed high
Status_Fan speed high
1 bit
DPT_Switch
1.001
R
T
1-Speed high active, 0-Speed high not active
Control_Fan speed high+
1 bit
DPT_Switch
1.001
W
1-Set fan speed high+
Status_Fan speed high+
1 bit
DPT_Switch
1.001
R
T
1-Speed high+ active, 0-Speed high+ not active
Control_Fan speed Man/Auto
1 bit
DPT_Switch
1.001
W
0-Manual; 1-Auto
Status_Fan speed Man/Auto
1 bit
DPT_Switch
1.001
R
T
0-Manual; 1-Auto
VANE POS
Control_Vane position enumerated
1 byte
Non-standarized
5.x
W
1-Position 1..7-Position 7
Status_Vane position enumerated
1 byte
Non-standarized
5.x
R
T
1-Position 1..7-Position 7
Control_Vane position scaling
1 byte
DPT_Scaling
5.001
W
Thersholds(0..21%;22..36%;37..50%;51..64%;65..79%;8
0..93%; 94..100%)