Intesis
TM
KNX
– BACnet Client
User Manual r1.2 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
18 / 26
6.
(Recipient type: Address (MAC)) Network
: Destination network, 0..65535. 0 for local network, 65535 for
broadcast (all networks).
7.
(Recipient type: Address (MAC)) MSTP MAC Address
: MAC address 0..255 of the BACnet server device.
8.
Reading type
: Related to service that will be used to read the BACnet server device. Options are Polling
(ReadProperty), COV, COV-unconf (unconfirmed COV), Polling Multiple (ReadPropertyMultiple).
9.
Write priority
: priority with which writes will be performed. Default is (none) (no priority), can be chosen from
1 (highest) to 16 (lowest) and none.
10.
COV Lifetime
: Periodic timeout at which COV subscription will be renewed.
•
BACnet scan functionality
Devices Configuration section includes functionality to scan the BACnet network for existing BACnet servers and
their objects.
To access this Scan functionality window, make sure that you’re online/connected with the device and click on
Scan
button.
Figure 5.6
BACnet Network scan button
If properly connected to the Intesis, following dialog will appear:
Figure 5.7
BACnet Network scan dialog