background image

Intesis

TM

 

KNX 

– BACnet Client

 

 

 

                                             

User Manual r1.2 EN

 

 

  

 

 

 

 

 

© HMS Industrial Networks S.L.U - All rights reserved

 

This information is subject to change without notice

 

 

  URL 

  

 http

s

://www.intesis.com  

 
 

                21 / 26

 

 

 

Device INBACSAM---O000 (200) 

 

Device INBACDAL---0000 (246) 

 
The 

BACnet 

objects 

that 

will 

be 

integrated 

in 

configuration 

are 

O01U00_Setpoint_S

 

and 

O01U00_Room_Temperature

 for 

Device INBACSAM---O000

, and those selected for 

Device INBACDAL---0000 

(can 

be seen when device is selected in the list at the left part of the window). 
 
Next  step  is  to transfer  those  objects  to MAPS  configuration. To  do  so,  it  must  be  first  selected  if  those  selected 
objects  are  meant  to  replace  the  entire  configuration  (

Replace  Devices

 

–  default)  or  added  to  existing  signals 

configuration (

Add Devices

). 

 

 

Figure 5.11 Apply

 button and selection on whether 

Replace

 or 

Add Devices

 

 

Apply

 button must be pressed then to transfer the results to the signals tab of the configuration. 

 

5.2.4  Signals 

All  available  objects,  Object  Instances,  its  corresponding  KNX  objects  and  other  main  parmaters  are  listed  in  the 
signals  tab.  More  information  on  each  parameter  and  how  to  configure  it  can  be  found  in  the  Intesis  MAPS  user 
manual for KNX. 
 

 

Figure 5.12 

Intesis MAPS Signals tab 

Summary of Contents for Intesis KNX

Page 1: ...KNX BACnet MSTP and BACnet IP client USER MANUAL Issue date 02 2020 r1 2 ENGLISH ...

Page 2: ...and are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables and requirements associated with any particular implementation HMS Industrial Networks cannot assume responsibility or liability for actual use based on the data examples or illustrations included in...

Page 3: ...hout notice URL https www intesis com 3 26 Gateway for the integration of BACnet MSTP and BACnet IP installations into KNX TP 1 home automation systems ORDER CODE LEGACY ORDER CODE INKNXBAC1000000 IBKNXBAC1000000 INKNXBAC2500000 IBKNXBAC2500000 INKNXBAC6000000 IBKNXBAC6000000 INKNXBAC1K20000 IBKNXBAC1K20000 INKNXBAC3K00000 IBKNXBAC3K00000 ...

Page 4: ...escription 9 Points definition 10 4 Connections 11 Powering the device 12 Connection to KNX 12 Connection to BACnet 12 4 3 1 BACnet IP 12 4 3 2 BACnet MSTP 12 Connection to the configuration tool 13 5 Set up process and troubleshooting 14 Pre requisites 14 Intesis MAPS Configuration monitoring tool for Intesis BACnet series 14 5 2 1 Introduction 14 5 2 2 Connection 14 5 2 3 Configuration tab 15 5 ...

Page 5: ... resources from a KNX home automation system as if it was a part of the own KNX installation and vice versa From BACnet point of view Intesis acts as a BACnet client device able to subscribe COV or perform periodic polling and writes on configured BACnet objects BACnet points values are available through its KNX interface acting in the KNX system as one more KNX device in it Configuration is carri...

Page 6: ...ering communication objects to access the BACnet objects of the configured external BACnet devices In the continuous polling of the BACnet server if an unresponsive BACnet server device is detected the corresponding virtual signal inside Intesis will be activated indicating communication error with the BACnet server device These virtual signals indicating communication status in real time with the...

Page 7: ...signal Analog Value Present Value Analog signal i e Temperature set point value Binary Input Present Value Digital signal i e ON OFF status Binary Output Present Value Digital signal i e ON OFF command Binary Value Present Value Digital signal i e ON OFF status command Multistate Input Present Value Multistate signal i e Working mode status Multistate Output Present Value Multistate signal Multist...

Page 8: ...d alternatively implement a BBMD itself Bacnet IP Broadcast Management Device This functionality facilitates communication of devices in other networks with the devices in the network where Intesis is installed Communication with BACnet IP excludes possibility of communicating with BACnet MSTP from Intesis BACnet MSTP When choosing BACnet MSTP device needs to be associated with a MAC address addre...

Page 9: ...for the point on the external BACnet device Consult documentation of BACnet device s to integrate for information about BACnet object instance of the points desired to integrate Note that configuration tool used with Intesis enables for discovery of existing BACnet devices in the network as well as their BACnet objects and types which can be later directly added in configuration This facilitates t...

Page 10: ...pend on the type of signal associated in the external system in every case In some integrations it is selectable in others it is fixed due to the intrinsic characteristics of the signal Group It is the KNX group to which the point is associated It is also the group to which the read R write W transmit T and update U flags are applied Is the sending group Listening addresses They are the addresses ...

Page 11: ...d is allowed through all the LAN path check the gateway user manual for more information Default IP is 192 168 100 246 DHCP is enabled by default PortA KNX Connect the KNX TP1 bus to connectors A3 and A4 of gateway s PortA Respect the polarity PortB BACnet MSTP Connect the EIA485 bus to connectors B1 B B2 A and B3 SNGD of gateway s PortB Respect the polarity Note for PortB Remember the characteris...

Page 12: ...e coupler that it is not filtering the telegrams from to the Intesis Connection to BACnet 4 3 1 BACnet IP Connect the communication cable coming from the network hub or switch to the ETH port Figure above of Intesis The cable to be used shall be a straight Ethernet UTP FTP CAT5 cable In case there is no response from the BACnet devices to the frames sent by Intesis check that they are operative an...

Page 13: ...13 26 Connection to the configuration tool This action allows the user to have access to configuration and monitoring of the device more information can be found in the configuration tool User Manual Two methods to connect to the PC can be used Ethernet Using the Ethernet port of Intesis USB Using the console port of Intesis connect a USB cable from the console port to the PC ...

Page 14: ... gateway Mini USB cable to connect to PC Link to download the configuration tool Product documentation Intesis MAPS Configuration monitoring tool for Intesis BACnet series 5 2 1 Introduction Intesis MAPS is a Windows compatible software developed specifically to monitor and configure Intesis KNX series The installation procedure and main functions are explained in the Intesis MAPS User Manual for ...

Page 15: ...e subsets of information are shown in this window General Gateway general parameters KNX KNX TP 1 interface configuration and BACnet Client BACnet interface parameters Figure 5 2 Intesis MAPS configuration tab General and KNX tabs are explained in Intesis MAPS user manual for Intesis KNX Series 5 2 3 1 BACnet Client Configuration Set the parameters for connection to BACnet network BACnet server de...

Page 16: ...this section following parameters should be configured 1 Mode Select whether Intesis is going to connect with BACnet IP or BACnet MSTP Rest of parameters in the section will be different depending on this 2 Mode IP UDP Port UDP port that will be used for BACnet IP communication It defaults to 47808 0xBAC0 3 Mode IP Network Role Related to capability of the device of communicating with devices from...

Page 17: ...es and their objects enabling to add them in the config See section BACnet scan functionality below for further detail Once a device is added following fields must be filled in for each device Figure 5 5 Devices configuration section 1 Device Name Device identifier within MAPS It will be used to reference the device from the signals table 2 Recipient Type Way in which the device will be identified...

Page 18: ...operty COV COV unconf unconfirmed COV Polling Multiple ReadPropertyMultiple 9 Write priority priority with which writes will be performed Default is none no priority can be chosen from 1 highest to 16 lowest and none 10 COV Lifetime Periodic timeout at which COV subscription will be renewed BACnet scan functionality Devices Configuration section includes functionality to scan the BACnet network fo...

Page 19: ...able scan of MSTP slave nodes by default only MSTP master nodes will be discovered If enabled Start MAC End MAC and Timeout in ms for the scan can be adjusted 5 MSTP Slaves through IP only when Explore Mode is IP In case that BACnet IP to MSTP routers are present in the BACnet IP network will enable scan of MSTP slaves through the corresponding BACnet IP router note that MSTP master nodes under a ...

Page 20: ...ose objects are to be scanned and clicking at Discover Checked Devices button This must be used with care when many devices are checked at once Resulting scan time can become very large Either way when having discovered objects under a BACnet device they are shown in the list at the right part of the window Figure 5 9 BACnet Explorer showing objects found under a BACnet device After objects have b...

Page 21: ...tep is to transfer those objects to MAPS configuration To do so it must be first selected if those selected objects are meant to replace the entire configuration Replace Devices default or added to existing signals configuration Add Devices Figure 5 11 Apply button and selection on whether Replace or Add Devices Apply button must be pressed then to transfer the results to the signals tab of the co...

Page 22: ...e Send button in the Receive Send section 5 2 6 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some specific tools and viewers In order to start using the diagnostic tools connection with the Gateway is required The Diagnostic section is composed by two main parts Tools and Viewers Tools Use the tools section to check the current hardwar...

Page 23: ... HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 23 26 Figure 5 14 Diagnostic More information about the Diagnostic section can be found in the Configuraion Tool manual ...

Page 24: ...der to avoid earth loops that can damage Intesis and or any other equipment connected to it we strongly recommend The use of DC power supplies floating or with the negative terminal connected to earth Never use a DC power supply with the positive terminal connected to earth The use of AC power supplies only if they are floating and not powering any other device 6 If you want to connect using IP co...

Page 25: ...tton A KNX programming button not used Button B Will broadcast I Am message in the BACnet network Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity Operational Humidity 5 to 95 no condensation Port A 1 x KNX TP 1 Plug in screw terminal block orange 2 poles 2500VDC isolation from other ports KNX power consumption 5mA Voltage rating 29VD...

Page 26: ...reserved This information is subject to change without notice URL https www intesis com 26 26 7 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting with space enough for external connections 100 mm h 100 mm w 130 mm d 56 mm h 88 mm w 90 mm d ...

Reviews: