12 (38)
5.2.2
Mounting the Device
Damage caused by overheating!
Ensure adequate air circulation. Observe the recommended mounting distance.
Use in dry rooms exclusively!
The device is designed for installation on a 35 mm DIN rail.
►
Ensure adequate air circulation and observe the recommended mounting distance.
–
If venting slots are covered: 2 cm distance on top and bottom
–
If venting slots are covered about 50 %: 1 cm distance on top and bottom
►
Use top hat rail mounting.
→
After installation the housing of the device is connected to functional earth.
►
Make sure, that the device is connected to the power supply (see
5.2.3
Cabling
Damaged device caused by reverse polarity or wrong power supply!
Make sure that power is connected with correct polarity and that power supply is of
recommended type.
The power supply must be a grounded circuit (PELV) and a 24 V DC ±15% regulated limited
power source according to EN 62368-1, annex Q, or IEC/EN 60950-1, clause 2.5.
►
Connect the cables to the power connector (
2/3/4
).
→
Device is grounded via the FE pin of the power connector (
2
).
►
To configure the device, connect the Ethernet port
ETH0
(
8
) or
ETH1
(
7
) directly to the
Ethernet port of the computer or via a hub or switch.
SG-basic User Manual
4.01.0401.20001 1.1 en-US