19
01.13
Jump frequency
By setting the jumping frequency and range, the frequency inverter can
avoid the mechanical resonance point of the load.
0.0
~
upper limit
frequency
0.0Hz
○
01.14
Jump range
0.0
~
10.0Hz
0.0Hz
○
01.15
Frequency
combination given
mode
0: Potentdigital frequency 1
1: Potentdigital frequency 2
2: PotentiAI
3: Digital frequency 1+AI
4: Digital frequency 2+AI
5: Digital frequency 1+ multi-speed
6: Digital frequency 2+ multi-speed
7: PotentMultistage Speed
8: AI+PLC (superposition in the same direction)
9: Reserved
0
~
9
0
×
01.16
Programmable
operation control
(simple PLC
operation)
LED bit: PLC enable control
0: invalid
1: valid
LED ten bits
:
Operation mode selection
0: single cycle
1
:
Continuous circulation
2
:
The final value is maintained after a single loop
LED hundred bits
:
starting mode
0
:
Restart from the first segment
1
:
Start from the stage of stop (failure) time
2: Start from the stage and frequency of stop (failure) time
LED thousand bits: power-off storage option
0: do not store
1: store
0000
~
1221
0000
×
01.17
Multi speed
frequency 1
Set the segment speed 1 frequency
-upper limit
frequency
~
upper
limit frequency
5.0Hz
○
01.18
Multi speed
frequency 2
Set the segment speed 2 frequency
-upper limit
frequency
~
upper
limit frequency
10.0Hz
○
01.19
Multi speed
frequency 3
Set the segment speed 3 frequency
-upper limit
frequency
~
upper
limit frequency
15.0Hz
○
01.20
Multi speed
frequency 4
Set the segment speed 4 frequency
-upper limit
frequency
~
upper
limit frequency
20.0Hz
○
01.21
Multi speed
frequency 5
Set the segment speed 5 frequency
-upper limit
frequency
~
upper
limit frequency
25.0Hz
○
01.22
Multi speed
frequency 6
Set the segment speed 6 frequency
-upper limit
frequency
~
upper
limit frequency
37.5Hz
○
01.23
Multi speed
frequency 7
Set the segment speed 7 frequency
-upper limit
frequency
~
upper
limit frequency
50.0Hz
○
01.24
Stage 1 running
time
Set the running time of segment speed 1 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.25
Stage 2 running
time
Set the running time of segment speed 2 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.26
Stage 3 running
time
Set the running time of segment speed 3 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.27
Stage 4 running
time
Set the running time of segment speed 4 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.28
Stage 5 running
time
Set the running time of segment speed 5 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.29
Stage 6 running
time
Set the running time of segment speed 6 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○
01.30
Stage 7 running
time
Set the running time of segment speed 7 (the unit is selected by [01.35],
and the default is seconds)
0.0
~
999.9s
10.0s
○