20
01.31
Stage Select 1 for
acceleration and
deceleration time
LED bit: Phase 1 acceleration and deceleration time
0
~
1
LED ten bits
:
Stage 2 Acceleration and deceleration time
0
~
1
LED hundred bits:Stage 3 Acceleration and deceleration time
0
~
1
LED thousand bits
:
Stage 4 Acceleration and deceleration time
0
~
1
0000
~
1111
0000
○
01.32
Stage Select 2 for
acceleration and
deceleration time
LED bit: Phase 5 acceleration and deceleration time
0
~
1
LED ten bits
:
Stage 6 Acceleration and deceleration time
0
~
1
LED hundred bits:Stage 7 Acceleration and deceleration time
0
~
1
LED thousand bits
:
Reserved
000
~
111
000
○
01.33
Acceleration
time 2
Set the acceleration and deceleration time 2
0.1
~
999.9s
0.4
~
4.0KW
10.0s
5.5
~
7.5KW
15.0s
10.0s
○
01.34
Deceleration
time 2
01.35
Time unit
selection
LED bit: process PID time unit
LED ten bits: simple PLC time unit
LED hundred bits: regular acceleration and deceleration time unit
LED thousand bits: reserved
0: 1 second
1: 1 minute
2: 0.1 second
000
~
211
000
×
01.36
Forward and
reverse dead
zone time
The transition time for the inverter to wait at the 0Hz during the transition
from the forward to the reverse operation, or from the reverse operation
to the forward.
0.0
~
999.9s
0.0
○
Group 02-analog and digital input and output parameters
Function
code
Name
Setting range
Minimum unit
Factory
setting
Change
02.00
AI input lower limit
Voltage
Set AI upper and lower limit voltage
0.00
~【
02.01
】
0.00V
○
02.01
AI input upper limit
Voltage
【
02.01
】~
10.00V
10.00V
○
02.02
AI lower limit
corresponding setting
Set AI upper and lower limits corresponding to the percentage of the
upper limit frequency [00.05].
-100.0%
~
100.0%
0.0%
○
02.03
AI upper limit
corresponding setting
100.0%
○
02.08
The analog input
Signal filtering time
constant.
This parameter is used to filter the input signals of AI and panel
potentiometer to eliminate the influence of interference.
0.1
~
5.0s
0.1s
○
02.09
Analog input
anti-shake deviation
limit
When the analog input signal fluctuates frequently near a given value,
the frequency fluctuation caused by this fluctuation can be
suppressed by setting 02.09.
0.00
~
0.10V
0.00V
○
02.10
Function Selection of
AO terminal
0:Output frequency
1
:
output current
2
:
revolving speed of motor
3
:
Output voltage
4
:
AI
5
:
Reserved
0
~
5
0
○
02.11
AO output lower limit
Set AO output upper and lower limit
0.00
~
10.00V
0.00
~
20.00mA
0.00V
○
02.12
AO output upper limit
10.00V
○
02.13
Input terminal DI1
function
0
:
idle control terminal
1: Forward JOG
2: Reverse JOG
3: Forward (FWD)
4: Reverse (REV)
5: Three-wire operation control
0
~
30
3
×