When the set frequency is lower than the lower limit frequency setting value (00.06), the inverter will run at the lower limit frequency.
2: After the shutdown
When the set frequency is lower than the lower limit frequency set value (00.06), the inverter will stop.
00.08
Digital setting of operating frequency
0.00Hz
~【
00.05
】
50.00
When the frequency channel is defined as digital reference, this function parameter is the digital frequency reference of the inverter panel and the initial setting
frequency of UP/DOWN.
00.09
Digital frequency setting 1 control
0000
~
2111
0000
LED units: power-down storage
0: store
When the inverter is powered on, the panel frequency increment is initialized to the value saved in the EEPROM at the last power-off.
1: Do not store
When the inverter is powered on, the panel frequency increment is initialized to 0.
LED ten digits: stop keeping
0: keep on stop
When the inverter stops, the frequency setting value is the final modified value.
1: Do not keep
When the inverter stops, the set frequency is restored to 00.08.
Hundreds of LEDs:
Negative frequency adjustment
0: invalid
1: Effective
When the selection is valid, operating the keyboard keys
can realize the positive and negative adjustment of the frequency.
Thousands of LED: PID, PLC frequency superposition selection
0: invalid
1:00.03+PID
The main frequency given channel and PID frequency are added together as the final given frequency of the inverter.
2:00.03+PLC
The main frequency given channel is added to the PLC frequency as the final given frequency of the inverter.
00.10
Acceleration time
0.1
~
999.9S
Model setting
00.11
Deceleration time
0.1
~
999.9S
Model setting
The acceleration time refers to the time required for the inverter to accelerate from zero frequency to the maximum output frequency, as shown in t1 in the figure
below. Deceleration time refers to the time required for the inverter to decelerate from the maximum output frequency to zero frequency, as shown in t2 in the figure
below.
There are two sets of acceleration and deceleration time parameters for this series of inverters. The acceleration and deceleration time of the other group is
defined in the function code 01.33
~
01.34. The factory default acceleration and deceleration time is determined by the model. If you want to select other acceleration
and deceleration time groups, Please select through the multi-function terminal (please refer to the function code 02.13
~
02.17). The acceleration and deceleration
time during jog operation are defined separately in 01.11 and 01.12.