16: The run command channel is forced to be a terminal
When this terminal is valid, the running command is forcibly converted from the current channel to terminal control, disconnect the terminal and return to the
previous running command channel.
17: The run command channel is forced to be communication
When this terminal is valid, the running command is forcibly converted from the current channel to communication control, disconnect the terminal, and return to
the previous running command channel.
18: Stop DC braking command
When this terminal is valid, the inverter directly switches to the DC braking state.
19: Frequency switch to AI
When this terminal is valid, the inverter frequency setting switch AI.
20: frequency switch to digital frequency 1
When this terminal is valid, the inverter frequency setting switches to digital frequency 1.
21: frequency switch to digital frequency 2
When this terminal is valid, the inverter frequency setting switches to digital frequency 2.
22
:
Reserved
23: Counter clear signal
The terminal is short-circuited with GND to clear the internal counter and use it in conjunction with the 24th function.
24: Counter trigger signal
The count pulse input port of the internal counter receives a pulse, the count value of the counter increases by 1 (if the counting mode is down counting, then
decreases by 1), and the maximum frequency of the count pulse is 200 Hz.
25: Timer clear signal
The terminal is short-circuited with GND to clear the internal timer and use it in conjunction with function No. 26.
26: Timer trigger signal
The trigger port of the internal timer.
27: Acceleration and deceleration time selection
By selecting these function terminals to be valid, select the second type of acceleration and deceleration time.
28: Swing frequency pause (stop at the current frequency)
When the terminal is short-circuited with GND, the inverter suspends the swing frequency operation mode, the inverter frequency stops running at the current
frequency; the swing frequency operation continues after this terminal is invalid.
29: Swing frequency reset (return to center frequency)
When this function is selected, whether it is automatic or manual input mode, closing this terminal will clear the wobble frequency status information stored in the
inverter. After disconnecting this terminal, the wobble frequency restarts (if there is a preset frequency, run the preset frequency first).
30: External stop/reset signal input (STOP/RST)
In any control mode (panel control, terminal control, communication control), this terminal can be used to decelerate and stop the inverter.
Use the terminal to perform the fault reset function. It has the same function as the RESET key on the keyboard. Use this function to realize remote fault reset.
02.18
FWD/REV terminal control mode
0
~
5
0