48
When the actual timing time is ≥07.03 (set timing time), the indicator signal is output.
12: Counter detection signal
When the count detection value is reached, the output indicator signal will be cleared until the count reset value is reached. Please refer to the description of
function code 07.02.
13: Counter reset signal
When the count reset value is reached, an indication signal is output, please refer to the description of function code 07.01.
14: auxiliary motor
Auxiliary motor and terminal function coordination process PID function module can realize simple one-to-two constant pressure water supply function.
15: Forward
When the inverter is in the forward running state, the output indicator signal.
16: Reverse
When the inverter is in the reverse running state, the output indicator signal.
17: Output indication signal when the output frequency drops to the speed detection level
When the output frequency of the inverter drops to the level of speed detection [02.25], an indication signal is output.
02.22
R close delay
0.0
~
255.0s
0.0
02.23
R open delay
0.0
~
255.0s
0.0
This function code defines the delay from the change of the state of the relay to the change of the output.
02.24
Frequency reaches FAR detection amplitude
0.0Hz
~
15.0Hz
5.0
When the output frequency is within the positive and negative detection width of the set frequency, the terminal outputs an effective signal (low level).
Figure 02-5 Schematic diagram of frequency arrival
02.25
FDT1 level setting value
0.0Hz
~
Upper limit frequency
10.0
02.26
FDT lag value
0.0
~
30.0Hz
1.0
When the output frequency of the inverter rises and exceeds the set value of FDT level, it outputs a valid signal (open collector signal, low level after the resistance is
pulled up), when the output frequency drops below the FDT signal (set Value- hysteresis value), an invalid signal (high impedance state) is output. As shown below: