58
05.07
Current limiting level
50
%~
200
%
160%
The current limiting level defines the current threshold of automatic current limiting operation, and its set value is the percentage relative to the rated current of the
inverter.
05.08
Feedback disconnection detection value
0.0
~
100.0%
0.0
%
This value is the percentage of PID given quantity. When the feedback value of PID is continuously less than the feedback disconnection detection value, the
inverter will make corresponding protection actions according to the setting of 05.00, and it will be invalid when 05.08=0.0%.
05.09
Feedback disconnection detection time
0.1
~
999.9S
10.0s
Delay time before protection action after feedback disconnection.
Figure 05-3 Timing diagram of closed-loop feedback loss detection
05.10
Inverter Overload pre-alarm level
0
~
150
%
120
%
The overload pre-alarm mainly monitors the overload condition of the inverter before the overload protection is activated. The overload pre-alarm level defines
the current threshold of the overload pre-alarm action, and its set value is the percentage relative to the rated current of the inverter.
05.11
Inverter Overload pre-alarm delay
0.0
~
15.0s
5.0s
The overload pre-alarm delay defines the delay time from the inverter output current continuously greater than the overload pre-alarm level (05.10) to the output
of the overload pre-alarm signal.
05.12
JOG priority enable
0
~
1
0
0: invalid
1: when the inverter is running, the jog priority is the highest
05.13
Oscillation suppression coefficient
0
~
200
30