OM-498 Page 38
10-8. Power Required To Start Motor
S-0624
1
Motor Start Code
2
Running Amperage
3
Motor HP
4
Motor Voltage
To find starting amperage:
Step 1: Find code and use table to
find kVA/HP. If code is not listed,
multiply running amperage by six to
find starting amperage.
Step 2: Find Motor HP and Volts.
Step 3: Determine starting amper-
age (see example).
Welding generator amperage out-
put must be at least twice the
motor’s running amperage.
VOLTS
AMPS
HP
230
2.5
1/4
Hz
PHASE
CODE
60
1
M
AC MOTOR
1
2
3
4
Single-Phase Induction Motor Starting Requirements
Motor Start
Code
G
H
J
K
L
M
N
P
KVA/HP
6.3
7.1
8.0
9.0
10.0
11.2
12.5
14.0
EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4
HP motor with a motor start code of M.
Starting the motor requires 12.2 amperes.
11.2 x 1/4 x 1000
230
= 12.2 A
kVA/HP x HP x 1000
VOLTS
= STARTING AMPERAGE
Volts = 230 HP = 1/4 Using Table, Code M results in kVA/HP = 11.2
10-9. How Much Power Can Generator Supply?
Ref. ST-800 396-A / S-0625
1
Limit Load To 90% Of
Generator Output
Always start non-resistive (motor)
loads in order from largest to small-
est, and add resistive loads last.
2
5 Second Rule
If motor does not start within 5
seconds, turn off power to prevent
motor damage. Motor requires
more power than generator can
supply.
1
2
Summary of Contents for 1435
Page 4: ......
Page 35: ...OM 498 Page 31 198 014 C Figure 9 2 Wiring Diagram For Welding Generator ...
Page 36: ...OM 498 Page 32 201 026 A Figure 9 3 Wiring Diagram For Auxiliary Power Panels 1 Of 2 ...
Page 37: ...OM 498 Page 33 201 026 A Figure 9 4 Wiring Diagram For Auxiliary Power Panels 2 Of 2 ...
Page 53: ...OM 498 Page 49 Notes ...
Page 58: ...OM 498 Page 54 Notes ...