OM-2226 / Operation and Maintenance Manual
60CU20 / Series 500062 / 400 Hz. Generator Set
May 2, 2013
Revision 2
Chapter 2-4
Page 16
Protective Circuit
NOTE:
Protective monitoring is not completely functional until the load contactor is CLOSED. Since it is not
advisable to vary voltages for test purposes while delivering power to an aircraft, the GPU should be
connected to a load bank for trouble shooting protective circuits. To avoid repetition, it will be assumed that
TEST/RESET
push-button switch has been pressed and the load contactor has been closed before
commencing each test.
Trouble, Symptom,
Condition
Probable Cause
Test, Check, and/or Remedy
1.
Load contactor
opens during power
delivery. Over
voltage fault
indicated.
a.
Over-voltage condition
may have been result of a
sudden drop in load, or
possible tampering with
REG potentiometer, and
may have been a normal
action.
Press
TEST/RESET
push-button switch and
resume power delivery. Observe voltmeter to be
certain voltage is normal 115 VAC. Adjust to
normal if necessary. If load contactor is opened
again and the fault code meter indicates an over-
voltage condition, proceed to step
b
.
b.
Defective CTL board
Use REG potentiometer to reduce voltage to 110
VAC. Observe voltmeter and gradually increase
voltage with potentiometer. If sensing circuit CTL
board opens the load contactor at any value less
than 125 VAC, it is defective. Replace CTL board.
2.
Load contactor
opens during power
delivery. Under
voltage fault
indicated.
a.
Under-voltage condition
may have been result of
a sudden shock load, or
possible tampering with
REG potentiometer, and
may have been a normal
action.
Press
TEST/RESET
push-button switch and
resume power delivery. Observe voltmeter to be
certain voltage is normal 115 VAC. Adjust to
normal if necessary. If load contactor is opened
again and the fault code meter indicates an under-
voltage condition, proceed to step
b
.
b.
Defective CTL board
Use REG potentiometer to reduce voltage to 100
VAC. Observe voltmeter and gradually decrease
voltage with potentiometer. If sensing circuit CTL
board functions to open load contactor at any value
great than 100VAC, it is defective. Replace CTL
board.
Summary of Contents for 500062-DLX
Page 2: ......
Page 4: ......
Page 6: ......
Page 209: ......
Page 210: ......
Page 211: ......
Page 212: ......
Page 213: ......
Page 214: ......
Page 215: ......
Page 216: ......
Page 217: ......
Page 218: ......
Page 219: ......
Page 220: ......
Page 221: ......
Page 222: ......
Page 223: ......
Page 224: ......
Page 225: ......
Page 226: ......
Page 227: ......
Page 228: ......
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ......
Page 233: ......
Page 234: ......
Page 235: ......
Page 236: ......
Page 237: ......
Page 238: ......
Page 239: ......
Page 240: ......
Page 241: ......
Page 242: ......